ABB ACH580-31 Quick Installation And Start-Up Manual - Page 11
Browse online or download pdf Quick Installation And Start-Up Manual for Industrial Equipment ABB ACH580-31. ABB ACH580-31 16 pages. Converter modules with electrolytic dc capacitors in the dc link
Also for ABB ACH580-31: Manual (16 pages)
Motor overload protection
The motor thermal overload protection can use motor temperature devices or can be estimated using a motor model
defined by parameters. The motor thermal overload protection is set to motor current and motor class curves as default. To
enable protection using motor model parameters or measurement devices, set parameter
35.55.
parameters through
?
Use the information key ( ) on the drive control panel for more information on setting group 35 parameters. You must set
the drive overload parameters correctly, or motor damage could occur.
Fieldbus communication
To configure the embedded fieldbus communication for Modbus RTU, you must set at least these parameters:
Parameter
20.01 Ext1 commands
22.11 Speed ref1 source
28.11 Frequency ref1 source
58.01 Protocol enable
58.03 Node address
58.04 Baud rate
58.05 Parity
58.06 Communication control
Other parameters related to the fieldbus configuration:
58.14 Communication loss
action
58.15 Communication loss
mode
58.16 Communication loss
time
Warnings and faults
Warning
Fault
Aux. code
-
2281
Current calibration
A2B1
2310
Overcurrent
A2B3
2330
Earth leakage
A2B4
2340
Short circuit
3E00
3130
Input phase loss
-
3181
Wiring or earth fault
A3A1
3210
DC link overvoltage
A3A2
3220
DC link undervoltage
-
3381
Output phase loss
-
5090
STO hardware failure
A5A0
5091
Safe torque off
A7CE
6681
EFB comm loss
A7C1
7510
FBA A communication
A7AB
-
Extension I/O
configuration failure
AFF6
-
Identification run
-
FA81
Safe torque off 1 loss
-
FA82
Safe torque off 2 loss
To adjust motor class curves (default is class 20), change parameters
Setting
Description
Embedded
Selects fieldbus as the source for the start and stop commands when
fieldbus
EXT1 is selected as the active control location.
EFB ref1
Selects a reference received through the embedded fieldbus interface
as speed reference 1.
EFB ref1
Selects a reference received through the embedded fieldbus interface
as frequency reference 1.
Modbus RTU
Initializes embedded fieldbus communication.
1 (default)
Node address. There must be no two nodes with the same node
address on-line.
19.2 kbps (default) Defines the communication speed of the link. Use the same setting as
in the master station.
8 EVEN 1 (default)
Selects the parity and stop bit setting. Use the same setting as in the
master station.
Refresh settings
Validates any changed EFB configuration settings. Use this after
changing any parameters in group 58.
58.17 Transmit delay
58.25 Control profile
58.26 EFB ref1 type
Description
Fault: Output phase current measurement fault.
The output current is more than the internal limit. This can also be caused by
an earth fault or phase loss.
A load unbalance that is typically caused by an earth fault in the motor or the
motor cable.
There is a short-circuit in the motor or the motor cable.
The intermediate DC circuit voltage oscillates due to missing input power
line phase.
Incorrect input and motor cable connection.
Intermediate DC circuit voltage is too high.
Intermediate DC circuit voltage is too low.
All three phases are not connected to the motor.
STO hardware diagnostics has detected hardware failure. Contact ABB.
The Safe torque off (STO) function is active.
Break in embedded fieldbus communication.
Communication lost between drive (or PLC) and fieldbus adapter.
The I/O extension module types and locations specified by parameters do
not match the detected configuration.
The motor ID run occurs at the next start.
The Safe torque off circuit 1 is broken.
The Safe torque off circuit 2 is broken.
58.28 EFB act1 type
58.31 EFB act1 transparent
source
58.33 Addressing mode
35.11
and subsequent
35.56
35.57
and
.
58.34 Word order
58.101 Data I/O 1
...
58.114 Data I/O 14
11