ABB Eagle Manual - Page 10
Browse online or download pdf Manual for Industrial Equipment ABB Eagle. ABB Eagle 20 pages. Self-powered single phase recloser for up to 27kv
Also for ABB Eagle: Quick Start Manual (4 pages)
10
E A G L E SELF-POWERED SINGLE PHASE RECLOSER
—
Mounting
Easy Replacement of Existing Equipment
Pole Mounted Hydraulic Recloser Replacement
Easily replace an existing hydraulic single phase
recloser by using a standard double insulator
mount with varying mount spacing
configurations.
A
Mounting Variations
Three reclosers – one for each phase, can be
mounted on the same pole for a three-phase
configuration.
3-Phase Configuration
A
DIMENSION "A"
REPLACEABLE COOPER RECLOSERS
12"
Type E, 4E, V4E, 4H, V4H, L, V4L
11.25"
Type D
23.25"
Type DV
Crossarm Mounted Fuse Cutout Replacement
Easily replace an existing fuse cutout by using a
20° double insulator mount or simply add the ABB
Eagle in parallel to the existing cutout (with the
fuse tube removed).
Double Insulator with 11.25"
and 12" Mount Spacing
Double Insulator with 20°
Crossarm Mount
Double Insulator with
23.25" Mount Spacing