ABB RHD8000 Series Instructions Manual - Page 12
Browse online or download pdf Instructions Manual for Controller ABB RHD8000 Series. ABB RHD8000 Series 17 pages. Electrical part turn actuators for continuous modulating control (contrac)
10.
Setup
12
The basic settings (definition of end positions) can be made via the Local Control Panel
(LCP). It is used for adapting the actuator to the operating range and the effective di-
rection without a PC. The actuator can be set up and configured completely using the
appropriate configuration program.
The commissioning and service field is located on the electronics!
10.1 Setup via LCP
10.1.1
Operating elements
1. Write-protect switch
2. LED for 100% position
3. Drive buttons
4. Reset button
5. Power LED
6. RS 232 socket
7. Potential toggle switch
8. LED for 0% position
9. Accept button (0%)
10. Accept button (100%)
5
10
4
9
8
1
Figure 12: Local Control Panel (LCP)
The actuator range is not preset in factory!
10.1.2
Initial situation
-
Electronics connected to power supply and actuator
-
Write-protect switch (1) set to "OFF" position
-
Electronics in operating mode "MAN" (no signal on DI 1)
-
No fault (if a fault occurs, both LEDs flash alternately at 4 Hz)
10.1.3
Setup procedure
-
Undo the screws of the LCP cover
-
Swing the cover to the side
(Default setting: OFF)
Indication if adjustment procedure, saved position, or
fault by different flash frequencies.
Press to cause drive motion
Press to restart processor and clear any 0% and 100%
values.
Indicates available mains supply
Connection socket to PC
Connection of reference potential to the system or pro-
tective earth (by default set to system)
Indication if adjustment procedure, saved position, or
fault by different flash frequencies..
Press to define current position as 0%; simultaneously
press push button 11 to complete the adjustment proce-
dure.
Press to define current position as 100%; simultaneously
press push button 10 to complete the adjustment proce-
dure
2
3
7
6
(r0110rxa)