ABB FPBA-01 PROFIBUS DP Quick Installation And Start-Up Manual - Page 2
Browse online or download pdf Quick Installation And Start-Up Manual for Control Unit ABB FPBA-01 PROFIBUS DP. ABB FPBA-01 PROFIBUS DP 2 pages. Profibus dp adapter module
Also for ABB FPBA-01 PROFIBUS DP: Quick Installation And Start-Up Manual (2 pages)
Connection procedure
It is recommended to use a PROFIBUS-
approved D-SUB 9 connector. These
connectors have a built-in termination network
and inductors for station capacitance
compensation.
Connect the cable to the D-SUB connector as
shown in this figure.
Start-up
When the module is connected to the drive, the drive control program sets the applicable parameters.
See the appropriate drive manual.
Basic parameter settings
Index
Name
20.01
Ext1 commands
22.11
Speed ref1 source
28.11
Frequency ref1 source
50.01
FBA A enable
50.02
FBA A comm loss func
51.02
Node address
51.05
Profile
52.01
FBA A data in1
52.02
FBA A data in2
53.01
FBA A data out1
53.02
FBA A data out2
To take the settings into use, validate and refresh the parameters with parameter 51.27 FBA par refresh.
Further information
See the latest version of FPBA-01 PROFIBUS DP adapter
module user's manual (3AFE68573271 [English]) in ABB
library (www.abb.com/drives/documents)
FPBA-01 manual
3AXD50000158188 Rev A (EN) 2017-11-23
Value
Fieldbus A
FBA A ref 1
FBA A ref 1
Enable (or select the option slot in which the module is installed)
Fault
Set the node address of the module according to the network configuration.
The ABB Drives communication profile is the default value.
SW 16bit
Act 16bit
CW 16bit
Ref1 16bit
For more information on fieldbus options and protocols
provided by ABB Drives, see the fieldbus
communications web page
.
(new.abb.com/drives/connectivity/fieldbus-connectivity).
1A
1B
2A
2B
OUT
IN
Fieldbus communications web page
Grounding clamp/
Strain relief