Baumer HMG 10-B-Profibus DP Handleiding voor installatie en gebruik - Pagina 19

Blader online of download pdf Handleiding voor installatie en gebruik voor {categorie_naam} Baumer HMG 10-B-Profibus DP. Baumer HMG 10-B-Profibus DP 32 pagina's. Absolute encoder with magnetic sensing

5.1.4
View in bus connecting box Profibus DP [A]
Terminal assignment
A
B
UB
GND
i
Terminals of the same significance are internally connected and identical in their
functions. Max. load on the internal terminal connections UB-UB and GND-GND
is 1 A each.
5.1.5

Setting for the terminating resistors

ON = Last user
OFF = User xx
5.1.6

Setting for the user address

Address can be set by rotary switches. Example: User address 23
MB246EN - 11171695, 17A2, Baumer_HMG10-ProfibusDP_II_EN
Negative serial data transmission, pair 1 and pair 2
Positive serial data transmission, pair 1 and pair 2
Voltage supply 10...30 VDC
Ground for UB
ELECTRICAL CONNECTION / PROFIBUS DP
Setting for the terminating resistors
Setting for the user address