Atkinson Electronics GSCM Handmatig - Pagina 11

Blader online of download pdf Handmatig voor {categorie_naam} Atkinson Electronics GSCM. Atkinson Electronics GSCM 16 pagina's. Generator start control module
Ook voor Atkinson Electronics GSCM: Bedienings- en installatie-instructies (16 pagina's)

Atkinson Electronics GSCM Handmatig
Electric Start High Speed Gas/ Propane Generator with Starter Control Box
This application matches most high speed or portable generator sets that have an electric starter and some type of starter control.
These generators should have the ignition switch left in the on position. The start commands usually come through the GSCM
connected to the remote start terminals. The remote start may be either momentary or maintained.
The K2 (crank) relay is used to switch the start input which is looking for a momentary signal. The K2 (crank) relay opens when the
generator has reached 30Hz, or half speed. If this setting doesn't allow the start input to remain engaged long enough for the
generator to stay on-line, adjust the run disconnect setting to 55Hz. See GSCM INITALIZATON AND ADJUSTMENT for changing
adjustments. The K4 (shutdown) relay provides a momentary stop signal until the generator AC Hz has dropped to zero.
The K3 (ignition) relay provides a continuous run signal for
generators requiring a maintained start signal. The K4
(shutdown) relay provides a momentary stop signal until
the generator AC Hz has dropped to zero.
www.atkinsonelectronics.com
800.261.3602
A double pole kill switch wired and installed by the user
stops the generator instantly in emergency situations such
as a fuel spill. One switch pole (N.C.) kills power to the
GSCM opening all relays. The other switch pole (N.O.)
shorts out the magneto for an instant stop.
11
Circuit Board Division
Revised 09/18