Atkinson Electronics GSCM Bedienings- en installatie-instructies - Pagina 10
Blader online of download pdf Bedienings- en installatie-instructies voor {categorie_naam} Atkinson Electronics GSCM. Atkinson Electronics GSCM 16 pagina's. Generator start control module
Ook voor Atkinson Electronics GSCM: Handmatig (16 pagina's)
GENERATOR START CONTROL MODULE
GSCM
APPLICATION 2 - ELECTRIC START HI SPEED GAS/PROPANE GENERATOR W/O STARTER CONTROL BOX
This application matches high speed generators that do not include starter control boxes. Propane generators may be the type
that ground the ignition to shutdown or have an automotive type coil ignition. The wiring configurations are shown for both
automotive and magneto type with or without fuel valves. High speed (3600 RPM) generators may need the crank disconnect
hertz adjustment set to 20Hz or less to avoid over driving the starter.
APPLICATION 3 - LOW SPEED GAS/PROPANE GENERATOR WITH SAFETIES
The low speed gas/propane generators also wire the same as in Application 2. However, the installer should determine ignition
type and oil and high temperature safety shutdown wiring. The GSCM is looking for oil and high temperature safety switches that
short to ground on a low oil pressure or high temperature condition.
ATKINSON ELECTRONICS, INC.
REV 8/06
Web Site: www.atkinsonelectronics.com
Distributed by: