Andivi – TRC-D – Technical Manual
READ INPUT REGISTER (FUNCTION CODE 04)
Function
Register
code
address
04
1
Current temperature
04
2
Fan speed
04
3
Cooling controller
04
4
Heating controller
04
5
Cooling valve output
04
6
Heating valve output
04
7
Temperature of built-in sensor
04
8
Temperature of external sensor
04
9
Software version
NOTICE:
If a value of a register is changed on the room controller (with buttons), a next write command to "this value" will be ignored,
and the room controller will not reply back anything. Those registers are:
1. Modbus Function 05,15 register address 01.
2. Modbus Function 06,16,23 register address 01~48.
For example, if users re-set the set-point value with buttons, a next Modbus command Fun.06/16/23 reg. address 01 from DDC/
BMS will be ignored and the room controller will not reply back any to DDC/BMS sent. (Note: While a value of a register is chang-
ing on the room controller (with buttons), any write command to "this value" will be ignored, but the room controller will reply
back the same data which DDC/BMS sent.)
This special strategy is integrated because registers must be changeable on both sites (master and slave).
18
08/14, fw. ver. V1.2, V1.3
Description
Definition
200~1000 (-20.0~100.0°C)
0: Off / 1: Stage I /
2: Stage II / 3: Stage III
0: Not active / 100: Active
0: Not active / 100: Active
0: Not active / 100: Active
0: Not active / 100: Active
-200~1000 (-20.0~100.0°C)
-200~1000 (-20.0~100.0°C)
10H~FFH (V1.0~VF.F)