ATL ATL-982 Gebruiksaanwijzing - Pagina 6
Blader online of download pdf Gebruiksaanwijzing voor {categorie_naam} ATL ATL-982. ATL ATL-982 6 pagina's. Fire display panel
A JB-FSD-982 fire display panel consists of a base and a display panel. It is subject to a wall-mounted
installation. Its external wires may be directly connected with the terminals on the rear panel of the
display panel. See Fig.9 for the schematic diagram of the mounting base of the display panel.
Base fixing: Fix the base of the display panel on the embedded box.
Wiring: Connect the leads stretching out from the junction box with the terminals on the display panel
and do a correct wiring according to the contents marked on the terminals.
Fix the display panel.
Arrange the guide slot on the back of the display panel so it aligns with the mounting base and press the
display panel with a downward force along the wall until the guide slot fits the mounting base perfectly.
After that, lock the small hook on the upside of the back of the display panel with the guiding sheet on the
mounting base with some matched screws (see Fig.9).
Precautions
Please inspect whether or not the circuit of the equipment suffers short circuit, open circuit, wrong wiring
and other defects.
The display panel is a precise electronic product and therefore needs to be managed by a specific
person. No other persons are allowed to operate it without permission.
Please wipe the surface of the equipment with alcohol.
VII. Fault analysis and troubleshooting
Fault
phenomenon
The display panel fails
to display or has an
abnormal display after
being started.
The equipment cannot
be started.
The fire alarm control
panel
cannot
be
registered.
The display panel has
abnormal
communication.
Possible cause
a. The power supply is abnormal;
b. The connection with the fire alarm
control panel is poor; or
c. The LCD or the CPU are damaged.
The
DC
24V
power
connected.
The RS-485 bus is poorly or wrongly
connected.
The system chosen is not proper and the
eighth digit of the dial switch is wrongly
pulled.
Page 6 of 6
Troubleshooting method
a. Inspect the DC24V power
supply;
b. Inspect the power line; or
c. Send the display panel back
to the factory for repair.
supply
is
not
Inspect the DC24V power
supply.
Inspect the RS-485 bus and
reconnect it.
Pull the eighth digit of the dial
switch to the correct position.
Remarks