AuCom CSXI-045 Gebruikershandleiding - Pagina 2

Blader online of download pdf Gebruikershandleiding voor {categorie_naam} AuCom CSXI-045. AuCom CSXI-045 13 pagina's.

MECHANICAL INSTALLATION

2
Mechanical Installation
2.1

Dimensions and Weights

A
Model
mm
(inch)
CSXi-007
CSXi-015
CSXi-018
98
CSXi-022
(3.85)
CSXi-030
CSXi-037
CSXi-045
145
CSXi-055
(5.70)
CSXi-075
CSXi-090
200
CSXi-110
(7.87)
2.2

Physical Installation

CSXi-007 ~ CSXi-055: Allow 100 mm (3.9 inch) between soft starters.
CSXi-075 ~ CSXi-110: Allow 200 mm (7.9 inch) between soft starters.
CSXi-007 ~ CSXi-055: Allow 50 mm (2.0 inch) between the soft starter and solid surfaces.
CSXi-075 ~ CSXi-110: Allow 200 mm (7.9 inch) between the soft starter and solid surfaces.
Soft starters may be mounted side by side with no clearance (that is, if mounted without
communications modules).
The soft starter may be mounted on its side. Derate the soft starter's rated current by 15%.
Page 2
B
C
D
mm
mm
mm
(inch)
(inch)
(inch)
82
201
188
(3.22)
(7.91)
(7.40)
124
215
196
(4.88)
(8.46)
(7.71)
160
240
216
(6.29)
(9.44)
(8.50)
CSXi
E
F
G
mm
mm
mm
(inch)
(inch)
(inch)
165
55
90.5
(6.49)
(2.16)
(3.6)
193
-
110.5
(7.59)
(4.4)
214
-
114.5
(8.42)
(4.5)
H
Weight
mm
kg
(inch)
(lb)
23
2.2
(0.9)
(4.85)
37
4.0
(1.5)
(8.81)
51
6.5
(2.0)
(14.33)
710-02408-00H