ADEMCO ADEMCO VISTA-20PSIA Handleiding voor programmering - Pagina 4

Blader online of download pdf Handleiding voor programmering voor {categorie_naam} ADEMCO ADEMCO VISTA-20PSIA. ADEMCO ADEMCO VISTA-20PSIA 17 pagina's. Ademco vista series security system
Ook voor ADEMCO ADEMCO VISTA-20PSIA: Snelle installatiehandleiding (2 pagina's), Gebruikershandleiding (20 pagina's), Snelle installatiehandleiding (2 pagina's), Snelle installatiehandleiding (2 pagina's), Beknopte handleiding (2 pagina's)

ADEMCO ADEMCO VISTA-20PSIA Handleiding voor programmering
∗ ∗ ∗ ∗ 49
Split/Dual Reporting
0 = Standard/backup reporting only (all to primary)
Primary Phone No.
1 = Alarms, Restore, Cancel
2 = All except Open/Close, Test
3 = Alarms, Restore, Cancel
4 = All except Open/Close, Test
5 = All
∗ ∗ ∗ ∗ 50
Burglary Dialer Delay
Delay Time:
0 = no delay UL: must be "0"
1 = 15 seconds; 2 = 30 seconds; 3 = 45 seconds
SIA Guidelines: delay must be minimum of 30 seconds
V20PSIA/V15PSIA:
Delay Time: 1 = 15 seconds; 2 = 30 seconds; 3 = 45 seconds
Delay Disable:
0 = use delay set in entry 1
1 = dial delay disabled for zones listed in zone list 6 (use zone list 6
to enter those zones that require dial delay to be disabled;
these zones ignore the setting in entry 1)
UL: Dial delay plus entry delay must not exceed one minute; use zone
list 6 to disable dial delay from appropriate zones, if necessary.
∗ ∗ ∗ ∗ 53
SESCOA/Radionics Select
0 = Radionics (0-9, B-F); enter "0" for all non-SESCOA formats
1 = SESCOA (0-9 only reporting)
∗ ∗ ∗ ∗ 54
Dynamic Signaling Delay
Select delay from 0 to 225 secs, in 15-sec increments.
0 = no delay (both signals sent); 1 = 15 secs; 2 = 30 secs, etc.
UL: Grade AA must be "0;" Grade A must be "15" max
∗ ∗ ∗ ∗ 55
Dynamic Signaling Priority
0 = Primary Dialer first; 1 = Long Range Radio first.
For UL Commercial Burglary installations that use a DACT and LRR,
this field must be "0".
∗ ∗ ∗ ∗ 56
∗ ∗ ∗ ∗ 57
∗ ∗ ∗ ∗ 58

Menu Modes

,
,
These are Menu Mode commands, not data fields, for Zone Programming,
Function Key Programming, and Expert Mode Zone Programming respectively.
See page 2 and respective sections later in this document.
TO PROGRAM SYSTEM STATUS, & RESTORE REPORT CODES (∗ ∗ ∗ ∗ 59 thru
∗ ∗ ∗ ∗ 68, *70 thru ∗ ∗ ∗ ∗ 76, and ∗ ∗ ∗ ∗ 89):
For 3+1 or 4+1 Standard Format: Enter a code in the first box: 1–9, #+10 for
0, #+11 for B, #+12 for C, #+13 for D, #+14 for E, #+15 for F.
A 0 ( not #+10) in the first box will disable a report. A 0 ( not #+10) in the
second box will result in automatic advance to the next field.
For Expanded or 4+2 Format: Enter codes in both boxes (1st and 2nd digits)
for 1–9, 0, or B–F, as described above.
A 0 ( not #+10) in the second box will eliminate the expanded message for
that report. A 0 ( not #+10) in both boxes will disable the report.
For Ademco Contact ID® Reporting: Enter any digit (other than 0) in the first
box, to enable zone to report (entries in the second boxes are ignored).
A 0 ( not #+10) in the first box disables the report.
UL: see installation instructions for requirements

SYSTEM STATUS REPORT CODES

∗ ∗ ∗ ∗ 59
Exit Error Alarm Report Code
See above for entries.
V20PSIA/V15PSIA:
∗ ∗ ∗ ∗ 60
Trouble Report Code
∗ ∗ ∗ ∗ 61
Bypass Report Code
∗ ∗ ∗ ∗ 62
AC Loss Report Code
∗ ∗ ∗ ∗ 63
Low Bat Report Code
∗ ∗ ∗ ∗ 64
Test Report Code
Use Scheduling mode to set periodic test reports, or use the following
key commands:
installer code +[#] + [0] + 0 = test report sent every 24 hours
installer code +[#] + [0] + 1 = test report sent once per week
installer code +[#] + [0] + 2 = test report sent every 28 day
Each mode sets schedule 32 (VISTA-20P) or schedule 08 (VISTA-15P)
to the stated repeat option; first test report sent 12 hours after command.
∗ ∗ ∗ ∗ 65
Open Report Code
[0]
2nd Phone No.
Others
Open/Close, Test
All
All
All
[2,0]
Delay Time
V20PSIA/V15PSIA
Delay Disable
[0]
[0]
[0]
( ✱ 59– ✱ 68)
[0]
[1] Always enabled.
[00]
|
[00]
|
[00]
|
[00]
|
[00]
|
[0,0,0]
Part. 1
Part. 2 Common
∗ ∗ ∗ ∗ 66
Arm Away/Stay Rpt Code
Away
Stay
Away
Part. 1
∗ ∗ ∗ ∗ 67
RF Trans. Low Bat Report Code
UL: must be enabled if wireless devices are used
∗ ∗ ∗ ∗ 68
Cancel Report Code
V20PSIA/V15PSIA:
∗ ∗ ∗ ∗ 69
Recent Closing Report Code
V20PSIA/V15PSIA:
Always enabled.
Field does not apply to other controls.
RESTORE REPORT CODES ( ✱ 70 – ✱ 76)
∗ ∗ ∗ ∗ 70
Alarm Restore Rpt Code
∗ ∗ ∗ ∗ 71
Trouble Restore Rpt Code
∗ ∗ ∗ ∗ 72
Bypass Restore Rpt Code
∗ ∗ ∗ ∗ 73
AC Restore Rpt Code
∗ ∗ ∗ ∗ 74
Low Bat Restore Rpt Code
∗ ∗ ∗ ∗ 75
RF Trans. Lo Bat Rst Rpt Code
UL: must be enabled if wireless devices are used
∗ ∗ ∗ ∗ 76
Test Restore Rpt Code

OUTPUT AND SYSTEM SETUP (

∗ ∗ ∗ ∗ 77
Daylight Savings Time
Start/End Month
0 = Disabled
1-12 = January-September (1 = Jan, 2 = Feb, etc)
#+10 = October; #+11 = November; #+12 = December
∗ ∗ ∗ ∗ 78
Daylight Savings Time
Start/End Weekend
0 = disabled; 1 = first; 2 = second; 3 = third; 4 = fourth;
5 = last; 6 = next to last; 7 = third to last
∗ ∗ ∗ ∗ 79
*80
*81
*82
Menu Modes
,
,
,
These are Menu Mode commands, not data fields, for Output Device Mapping,
Output Programming, Zone List Programming, and Alpha Programming
respectively. See page 2 and their respective sections in the Installation and
Setup Guide for procedures.
∗ ∗ ∗ ∗ 84
Auto Stay Arm
0 = no; 1 = partition 1 only; 2 = partition 2 only; 3 = both partitions
∗ ∗ ∗ ∗ 85
Cross Zone Timer
This option not for use in UL installations.
(assign cross zones on zone list 4, using *81 Menu mode)
0 = 15 seconds
1 = 30 seconds
2 = 45 seconds
3 = 60 seconds
4 = 90 seconds
5 = 2 minutes #+11 = 7 min
∗ ∗ ∗ ∗ 86
Cancel Verify Keypad Display
0 = no "alarm canceled" display
1 = display "Alarm Canceled" when system is disarmed after an alarm
has occurred. (To clear the "ALARM CANCELED" display, the
user must enter the security code + OFF again.)
∗ ∗ ∗ ∗ 87
Misc. Fault Delay Time
(used with Configurable Zone Types "digit 6")
0 = 15 seconds
1 = 30 seconds
2 = 45 seconds
3 = 60 seconds
4 = 90 seconds
5 = 2 minutes
UL: may only be used on non-burglar alarm/ non-fire alarm zones
when used in fire and/or UL burglar alarm installation
– 4 –
[0,0,0,0,0,0]
Stay
Away
Stay
Part. 2
Common
[00]
[00]
[10] Report enabled.
[11]
[00]
[00]
[00]
[00]
[00]
[00]
77 –
93)
[4][10]
[1][5]
6 = 2-1/2 min
#+12 = 8 min
7 = 3 min
#+13 = 10 min
8 = 4 min
#+14 = 12 min
9 = 5 min
#+15 = 15 min
#+10 = 6 min
6 = 2-1/2 min
#+12 = 8 min
7 = 3 min
#+13 = 10 min
8 = 4 min
#+14 = 12 min
9 = 5 min
#+15 = 15 min
#+10 = 6 min
#+11 = 7 min
|
|
|
[0]
|
|
|
|
|
|
|
|
[3]
[0]
[1]
[0]