ADEMCO 5817CB Installatie- en installatiehandleiding - Pagina 2

Blader online of download pdf Installatie- en installatiehandleiding voor {categorie_naam} ADEMCO 5817CB. ADEMCO 5817CB 2 pagina's. Wireless commercial / household transmitter
Ook voor ADEMCO 5817CB: Installatie-instructies (4 pagina's), Snelstarthandleiding (2 pagina's), Installatie-instructies (2 pagina's), Installatie- en installatiehandleiding (2 pagina's)

ADEMCO 5817CB Installatie- en installatiehandleiding
small screwdriver into the mounting plate release hole, push down
to retract the locking tab, and push upward on the unit to disengage
from posts. If not using the mounting plate, it is necessary to
remove the PC board from the case back. Slide a small flat bladed
screwdriver between the case back and PC board near the board
hold-down clip and carefully pry the board out.
7. In the area that was previously marked for the location of the
mounting plate, (step 4), install the hold-down tab with a 5/8" flat
head dry-wall screw. The tab must be aligned with the
corresponding slot in the case back as shown in Figure 2. The tab
as well as the case back must be anchored to a wall stud or other
solid wood material.
8. To reinstall the PC board into the case back, position the board onto
the two retaining studs on one side of the case back and snap the
board into place. The hold-down tab must mate with the
corresponding cutout in the case back after case back is installed.
9. Reverse the procedure of the first three steps to complete
reassembly of the unit.
10. Set the DIP switch (after the control panel has enrolled the
transmitter's input IDs) for the desired primary loop characteristics,
as described in the "Primary Loop Options Table".
3
Wiring Connections
Connect the loop wiring to the unit's terminals before installing the
battery (see Figure 3).
Notes:
a.
Primary loop 1 is a supervised loop and must have an end-of-line
(EOL) resistor (470K ohms, supplied) placed across the last
sensor. Additionally, for Primary loop 1, a contact device may not
be installed more than 20 feet from the transmitter.
b.
If loop 2 is not going to be used, the magnet is not necessary.
c.
If loop 3 is not going to be used, no connection is needed across
its terminals. For UL household burglary and fire installations, the
loop 3 contact device (if used) may not be more than 3 feet from
the transmitter.
4
Battery Installation/Replacement
1. Remove the transmitter's cover as described in Mounting Step 1.
2. Observe correct polarity and insert the battery provided into the
battery holder (see Figure 3). Take care not to bend the antenna.
Note: Replace battery only with: Duracell DL123A, DL123,
Panasonic CR123A or Ademco 466.
Risk of fire, explosion, and burns. Do not recharge,
disassemble, heat above 212°F (100°C), or incinerate.
Dispose of used batteries promptly. Keep away from
children.
3. To replace the cover, engage the hooks along the top edge and
snap shut.
For Limitations of the entire alarm system, refer to the control panel's
installation guide for the receiver/control with which this device is
used.
WARRANTY Go to:
http://www.security.honeywell.com/hsc/resources/wa/
DOCUMENTATION AND ONLINE SUPPORT Go to:
http://www.security.honeywell.com/hsc/resources/MyWebTech/
The user shall not make any changes or modifications to the equipment unless authorized by the Installation Instructions or User's Manual.
Unauthorized changes or modifications could void the user's authority to operate the equipment.
This device complies with Part 15 of the FCC Rules, and RSS 210 of IC. Operation is subject to the following two conditions:
(1) This device may not cause harmful interference.
(2) This device must accept any interference received, including interference that may cause undesired operation.
Cet appareil est conforme à la partie 15 des règles de la FCC & de RSS 210 des Industries Canada. Son fonctionnement est soumis aux conditions
suivantes: (1) Cet appareil ne doit pas causer d' interferences nuisibles. (2) Cet appareil doit accepter toute interference reçue y compris les
interferences causant une reception indésirable.
ÊK5623V2PŠ
K5623V2 1/09 Rev. B
FEDERAL COMMUNICATIONS COMMISSION STATEMENT
FCC / IC STATEMENT
PRIMARY LOOP OPTIONS TABLE
SWITCH
SET TO
1
ON
REPEATING
TRANSMISSION
(every 4 sec.)
UPON PRIMARY
LOOP FAULT
Use for high
priority alarm,
such as fire.
OFF
SINGLE
TRANSMISSION
PER PRIMARY
LOOP CHANGE-
OF-STATE
Notes: a. In order for the control panel to enroll the transmitter, the DIP
switches must be set to OFF – ON – ON – OFF (see Figure 3).
b. The Auxiliary loops are not affected by the DIP switch settings.
5
Testing
Regular maintenance and inspection (at least annually) by the installer are vital to
continuous satisfactory operation of any alarm system. The installer should instruct the
user to test the system frequently (at least weekly) to insure the system's operation at
all times, as well as offer a regular maintenance program to the user. The user should
also be acquainted with proper operation and limitations of the entire alarm system.
For testing procedures, refer to the User Guide or Installation and Setup Guide for the
system control panel.
UL Requirement
1. If using one of the panel revisions shown in the following table, and
programming the 5817CB as an Entry/Exit zone, you must enroll the
tamper loop (loop 4) as a separate zone, programmed for 24-hour
response (e.g., Zone type 5  Trouble-by-day/Alarm-by-night).
Model #
Rev.
FA1600C
8
Vista-32FB
3
Vista-128FB
4
Vista-128B
3
2. For UL Commercial Burglary installations, this transmitter must be used
in conjunction with the 5881ENHC RF Receiver.
Specifications
Dimensions:
1-9/16"W x 3-1/2"H x 1-3/16"D (40mm x 89mm x 30mm)
Battery:
3V Lithium (see BATTERY INSTALLATION/REPLACEMENT).
Signal Level: To determine ambient noise level and signal strength, refer to
compatible receiver Installation and Setup Guide.
NFPA-72 Compliant.
UL Listings:
Commercial Fire.......UL864
Household Fire.........UL985
Household Burg........UL1023
Commercial Burg......UL365, UL609, UL1076, UL1610
U L
For dry, indoor use only. Do not install in air-handling spaces.
Copyright  2009 Honeywell International Inc.
DIP SWITCH POSITION
2
3
SWITCH
SWITCH
MUST
MUST
ALWAYS BE
ALWAYS BE
IN THE
IN THE
ON
ON
POSITION
POSITION
EPROM P/N
(WAVIS150FA-18)
(WAVIS32FB-13)
(WAVIS128FB-14)
(WAVIS128B-13)
2 Corporate Center Drive, Suite 100
P.O. Box 9040, Melville, NY 11747
www.honeywell.com/security
4
SWITCH
MUST
ALWAYS BE
IN THE
OFF
POSITION