Aqua Flo AQUV-20R2 Gebruikershandleiding - Pagina 9
Blader online of download pdf Gebruikershandleiding voor {categorie_naam} Aqua Flo AQUV-20R2. Aqua Flo AQUV-20R2 16 pagina's. Ultraviolet disinfection system
Spring
Spring
Spring
8. From the top of the gland nut, drop the lamp spring into the quartz dome
Fig. 6C.
9. Holding the top 4-pin end of the lamp, carefully slide the lamp into the
quartz dome and attach the lamp pins to the lamp connector. The lamp
connector fits over the pins in only one orientation Fig. 6D.
10. Slide the lamp connector cover over the gland nut and tighten the black
screw on it Fig. 6E. Check tightening details, the black screw allows the cord to come through the plastic making it easy to hook up lamp, then
white plastic part has a little screw to secure it to the gland nut.
11. Remove the nut from the ground stud at the top of the unit. Next place the ground wire (green wire with yellow stripes) over the stud and
tighten the nut.
12. Connect the ballast power cable to the AC supply (with surge protector). The green lamp-on LED will light up and the display will show "365".
This number indicates the number of days left until lamp life expires and must be replaced. Follow Step (E) before consuming water.
YOUR AQUA FLO AQUV UV DISINFECTION SYSTEM IS NOW READY FOR SERVICE.
(E) DISINFECTION PROCEDURE
Before service begins, all household plumbing lines should be disinfected to prevent the possibility of re-contamination after UV disinfection. You
should also disinfect your plumbing system if the power goes out for several hours or more or if the unit has been accidentally shut-off for several
hours or more. It is advisable to disinfect the plumbing lines at least once a year. If the bypass is used, the water system of the house should be
disinfected in the same way it was in initial installation. Disinfect after using bypass as well.
The following is a general method for disinfection of plumbing lines. If you are uncertain about the
efficacy of this procedure you are advised to contact your local health authority responsible for water
safety.
1. Shut off the supply valve and de-pressurize the lines by opening a tap until it runs dry.
2. Remove the filter in the filter housing, add about 1-2 cups (250-500ml) of unscented household bleach (5 to 6% sodium hypochlorite) to the
empty filter housing and put it back on the filter head.
3. Open the supply valve and slowly open a faucet and let the water run until you can smell the chlorine and then shut the faucet off. Repeat the
procedure for all hot and cold outlets in the house. Add more bleach as required. Run hot faucets longer to allow the chlorine to come through
the hot water tank.
4. Leave the bleach solution in the plumbing system for about 6 to 8 hours preferably overnight.
Fig.6C
Lamp
Lamp
Lamp
Fig.6D
WARNING
Installing lamp without the spring in place can cause
breakage of quartz dome.
Fig.6E
9