CONNECTIONS :
Three-phase connection with or without neutral
Raccordement triphasé avec ou sans neutre
L1
L2
L3
N
Commissioning:
- Position the settings by turning all potentiometers fully
clockwise.
- Apply the voltage setting and check the phase rotation
display.
- Since this is correct, reduce the Umax detection threshold
by turning the potentiometer anti-clockwise.
As soon as the detection is displayed, bring the setting a few
degrees clockwise.
- Do the same for the other Umin and asymmetry settings.
- Adjust the timing as needed.
1
8
Quick connection between
the PAN45-01-00 front
display unit and the DIN
PH001 unit (cable supplied
with the PAN45-01-00).
CARACTERISTICS :
Supply
Nominal :
Minimum :
Consumed strength :
Frequency :
Settings :
Under pressure :
On voltage :
Asymmetry % :
Time delay :
Start-up times :
Instant protection
Loss of rotation :
On voltage :
Asymmetry % :
Asymmetry > +25%
Time delay :
Output contact :
Rated / Max intensity :
Rated / Max cut-off voltage :
Max cut-off power :
Number of operations :
Contact material :
Insulation between power supply
and contacts :
Enclosures
Protection :
Material :
Resistance to fl ame :
Humidity in use / storage :
Operating temperature :
Storage temperature :
Surface insulation :
Protection by 3 fuses
0,5A
LOAD
CHARGE
PH3
L4
L1
L2
L3
VR
VV
VB
1 -
2 -
3 -
1
8
4 -
PAN45-01-00
PH001
Three phase
Single phase
PH / PH
PH / N
150V- 480V
150V-280V
150V
150V
2VA
45-55Hz
300V - 380V
173V - 220V
380V - 480V
220V - 277V
5% - 25%
1s
<1s
Yes
No
Umax > +10% of the setting
or > 277v PH/N or 480v PH/PH
No
0,5s
1RT
8A / 10A
250Vac / 400Vac
2500VA / 300W
1x10
7
AgSnO2
5KV / 1mn
IP20
UL94 V2 class
90% non-condensing / 70%
-20°C / +60°C
-20°C / +70°C
10
15
Ohms/cm
L1
L
N
is compulsory.
Crossing neutral with a
phase can destroy the
device
In single-phase, the «overvoltage» and «undervoltage» as
well as «time delay» detections are active.
Phase rotation and asymmetry / loss of neutral are
inactive.
DIMENSIONS :
68
48
PH1
PH2
PH3
Status
45 à 50
ASSEMBLY / DISASSEMBLY :
PAN45-01-00
Powered by the PH001 box in 5V
through the RJ45 cable
COMMANDE:
- PH001 : Phase rotation controller in 380V
or 220v single phase, DIN box.
IP65 on front
- PAN45-01-00 : 4 LEDs display, 48x48, 5V
polyamide PA66 30gf
UL94 V2 class
voltage, mounting on the front of the cabinet,
90% non-condensing / 70%
supplied with RJ45 cable L = 2.00m (other
-20°C / +60°C
-20°C / +70°C
length on request).
10
15
Ohms/cm
3, Rue de la Garenne - Z.I. de Vernon
27950 SAINT MARCEL - FRANCE
tél. : +33 (0)2 32 51 47 16
Fax : +33 (0)2 32 21 13 73
http://www.ami-control.com
Single-phase connection
Raccordement monophasé
0,5A
LOAD
CHARGE
PAN45-01-00
5
45 +/- 0,3
A
B
Assembly (A) of the housing on the