ABB ACS580-01 drives Snelle installatie- en starthandleiding - Pagina 13

Blader online of download pdf Snelle installatie- en starthandleiding voor {categorie_naam} ABB ACS580-01 drives. ABB ACS580-01 drives 17 pagina's. Frequency converter. nec types
Ook voor ABB ACS580-01 drives: Handmatig (16 pagina's), Snelle installatie- en starthandleiding (17 pagina's)

ABB ACS580-01 drives Snelle installatie- en starthandleiding
Parameter
58.04 Baud rate
58.05 Parity
Other parameters related to the fieldbus configuration:
58.14 Communication loss
action
58.15 Communication loss
mode
58.16 Communication loss
time

Warnings and faults

Warning
Fault
Aux. code
A2A1
2281
Current calibration
A2B1
2310
Overcurrent
A2B3
2330
Earth leakage
A2B4
2340
Short circuit
-
3130
Input phase loss
-
3181
Wiring or earth fault
A3A1
3210
DC link overvoltage
A3A2
3220
DC link undervoltage
-
3381
Output phase loss
-
5090
STO hardware failure
A5A0
5091
Safe torque off
A7CE
6681
EFB comm loss
A7C1
7510
FBA A communication
A7AB
-
Extension I/O
configuration failure
AFF6
-
Identification run
-
FA81
Safe torque off 1
-
FA82
Safe torque off 2
Ratings, fuses and typical power cable sizes
ACS580
Nominal ratings
-01-...
Input
Output
current
current
I
I
I
1
1
N
(480 V)
A
U
= 3-phase 230 V
N
04A7-2
4.7
-
4.7
06A7-2
6.7
-
6.7
07A6-2
7.6
-
7.6
12A0-2
12.0
-
12.0
018A-2
16.9
-
16.9
025A-2
24.5
-
24.5
032A-2
31.2
-
31.2
047A-2
46.7
-
46.7
060A-2
60
-
60
089A-2
89
-
89
115A-2
115
-
115
144A-2
144
-
144
171A-2
171
-
171
213A-2
213
-
213
276A-2
276
-
276
U
=3-phase 400 V or 480 V
N
02A7-4
2.6
2.1
2.6
03A4-4
3.3
3.0
3.3
04A1-4
4.0
3.4
4.0
05A7-4
5.6
4.8
5.6
07A3-4
7.2
6.0
7.2
09A5-4
9.4
7.6
9.4
12A7-4
12.6
11.0
12.6
018A-4
17.0
14.0
17.0
026A-4
25.0
21.0
25.0
033A-4
32.0
27.0
32.0
Setting
Description
19.2 kbps (default) Defines the communication speed of the link. Use the same setting as
in the master station.
8 EVEN 1 (default)
Selects the parity and stop bit setting. Use the same setting as in the
master station.
58.17 Transmit delay
58.25 Control profile
58.26 EFB ref1 type
Description
Warning: Current calibration is done at the next start.
Fault: Output phase current measurement fault.
The output current is more than the internal limit. This can also be caused by
an earth fault or phase loss.
A load unbalance that is typically caused by an earth fault in the motor or the
motor cable.
There is a short-circuit in the motor or the motor cable.
The intermediate DC circuit voltage oscillates due to missing input power
line phase.
Incorrect input and motor cable connection.
Intermediate DC circuit voltage is too high.
Intermediate DC circuit voltage is too low.
All three phases are not connected to the motor.
STO hardware diagnostics has detected hardware failure. Contact ABB.
The Safe torque off (STO) function is active.
Break in embedded fieldbus communication.
Communication lost between drive (or PLC) and fieldbus adapter.
The installed C-type module is not the same as configured, or there is an
error in the communication between the drive and module.
The motor ID run occurs at the next start.
The Safe torque off circuit 1 is broken.
The Safe torque off circuit 2 is broken.
Motor
gG fuse (IEC
1)
60269)
power
I
P
ABB type
N
N
(480 V)
A
kW
hp
-
0.75
1.0
OFAF000H25
-
1.1
1.5
OFAF000H25
-
1.5
2.0
OFAF000H25
-
3.0
3.0
OFAF000H25
-
4.0
5.0
OFAF000H25
-
5.5
7.5
OFAF000H40
-
7.5
10.0
OFAF000H40
-
11.0
15.0
OFAF000H63
-
15
20
OFAF000H63
-
22
30
OFAF00H125
-
30
40
OFAF00H125
-
37
50
OFAF0H200
-
45
60
OFAF0H250
-
55
75
OFAF1H315
-
75
100
OFAF2H400
2.1
0.75
1.0
OFAF000H4
3.0
1.1
1.5
OFAF000H6
3.4
1.5
2.0
OFAF000H6
4.8
2.2
3.0
OFAF000H10
6.0
3.0
3.0
OFAF000H10
7.6
4.0
5.0
OFAF000H16
11.0
5.5
7.5
OFAF000H16
14.0
7.5
10.0
OFAF000H25
21.0
11.0
15.0
OFAF000H32
27.0
15.0
20.0
OFAF000H40
58.28 EFB act1 type
58.31 EFB act1 transparent
source
58.33 Addressing mode
Fuses
uR/aR fuse
UL class
2) 3) 4)
(DIN 43620)
T
Bussmann type
170M1563
JJS-15
170M1563
JJS-15
170M1563
JJS-15
170M1563
JJS-15
170M1563
JJS-30
170M1565
JJS-40
170M1565
JJS-40
170M1566
JJS-80
170M1566
JJS-80
170M3815
JJS-150
170M3815
JJS-150
170M3817
JJS-200
170M5809
JJS-250
170M5810
JJS-300
170M6810
JJS-400
170M1561
JJS-15
170M1561
JJS-15
170M1561
JJS-15
170M1561
JJS-15
170M1561
JJS-15
170M1561
JJS-15
170M1561
JJS-15
170M1563
JJS-30
170M1563
JJS-30
170M1565
JJS-40
58.34 Word order
58.101 Data I/O 1
...
58.114 Data I/O 14
Typical power cable
Frame
sizes, Cu
size
2
mm
AWG
3×1.5 + 1.5
18
3×1.5 + 1.5
16
3×1.5 + 1.5
16
3×1.5 + 1.5
14
3×2.5 + 2.5
10
3×4.0 + 4.0
8
3×6.0 + 6.0
8
3×10 + 10
6
3×10 + 10
4
3×35 + 16
2
3×50 + 25
1/0
3×70 + 35
3/0
3×95 + 50
4/0
3×120 + 70
300 MCM
2×(3×70 + 35)
2×2/0
3×1.5 + 1.5
16
3×1.5 + 1.5
16
3×1.5 + 1.5
16
3×1.5 + 1.5
16
3×1.5 + 1.5
16
3×2.5 + 2.5
14
3×2.5 + 2.5
14
3×2.5 + 2.5
14
3×6 + 6
10
3×10 + 10
8
13
R1
R1
R1
R1
R1
R2
R2
R3
R3
R5
R5
R6
R7
R7
R8
R1
R1
R1
R1
R1
R1
R1
R2
R2
R3