aquatherm 50341 Bedienings- en onderhoudshandleiding - Pagina 3
Blader online of download pdf Bedienings- en onderhoudshandleiding voor {categorie_naam} aquatherm 50341. aquatherm 50341 8 pagina's. Fusion for aquatherm green pipe, aquatherm blue pipe, aquatherm lilac pipe, aquatherm red pipe and aquatherm ti pipesystems from 16 up to 125 mm
PART A: gUIDELINEs
PART B: ChECkINg Of DEvICEs AND TOOLs
Part A: guidelines
17. For the correct handling of welding machines the following must be
observed:
General Regulations for Protection of Labour and Prevention of Accidents
and particularly the Regulations of the Employers' Liability Insurance Asso-
ciation of the Chemical Industry regarding Machines for the Processing of
Plastics, chapter: „Welding Machines and Welding Equipment".
18. For the handling of aquatherm- welding machines, devices and tools
please observe General Regulations DVS 2208 Part 1 of the German
Association for Welding Engineering, Registered Society (Deutscher Ver-
band für Schweißtechnik e. V.).
Part B: Checking of devices and tools
1. Check, if the aquatherm- welding devices and tools comply with to the
guidelines "Fusion Part A".
2. All used devices and tools must have reached the necessary operating
temperature of 260 °C. This requires acc. to "Fusion Part A, item 8" a
separate test, which is indispensable (DVS - Welding Guidelines):
Suitable measuring instruments have to measure a temperature of up to
350° C with a high accuracy.
NOTE:
aquatherm recommends the original aquatherm temperature measuring
device art.-no. 50188
PART B: PREPARATION fOR ThE fUsION
3. Cut the pipe at right angles to the pipe axis. Only use aquatherm pipe
cutters or other suitable cutting pliers. Take care that the pipe axis is free
from burrs or cutting debris and remove where necessary.
4. Mark the welding depth at the end of the pipe with the enclosed pencil
and template.
5. Mark the desired position of the fitting on the pipe and / or fitting. The
markings on the fitting and the uninterrupted line on the pipe may be used
as a guide.
Measurement of temperature at the aquatherm manual welding device (800W )
Measurement of temperature at the aquatherm welding machine
Measurement of temperature at the aquatherm butt-welding machine
Cutting of the pipe
Marking of the welding depth