LAMP AIMING
With unit open, loosen the nut
1
and screw and aim the lamp
head to the desired position.
DC output to the remote units.
AC input Connector
White: Neutral
Black: HOT 120-347Vac, 50/60Hz
DESOTO
LAMP AIMING and WIRING DIAGRAM
With lamp heads aimed, begin by
2
tightening the nut until the gasket is
fully compressed.
(Torque spec: 12 in-lbs)
WIRING DIAGRAM
Yellow/Red stripe (+)
Blue/Black stripe (-)
Heater
Connector
(CW Option Only)
TM
LIFE SAFETY SOLUTIONS
Hex Nut
Nylon Washer
Gasket
Screw
Lamp head
Battery
Connector
Connector
Status LED
Connector
Federal Communications Commission (FCC)
Requirements:
This device complies with FCC Title 47, Part 15, Subpart B.
This device does not cause harmful interference.
TEL: 740-345-9631
www.Holophane.com
With nut secure, tighten the screw to
3
finish aiming procedure.