Air Change WM-ERV Instrukcja instalacji i konserwacji - Strona 6
Przeglądaj online lub pobierz pdf Instrukcja instalacji i konserwacji dla Klimatyzator Air Change WM-ERV. Air Change WM-ERV 12 stron. Wall mount energy recovery ventilator
4 Remove heat exchanger by removing security screws, and drawing forward towards
yourself;
5 Cut aperture 715mm wide x 760mm high. The depth of the carcass is 595mm with an
additional 145 mm protruding face panel (see drawing);
6 The unit must be inserted from inside the room. Push unit through aperture until flange
seals against the wall;
7 Fix through bottom and through sides 460mm up from bottom;
8 Timber or metal sealing batons for the rear of the unit will need to be supplied by the
installer;
9 Replace fan drawer, heat exchanger and security screws, filter and front grille.
2.3
Electrical
• A power supply rated at 240v +/- 10% 1 phase, 50Hz is required to operate two
80W fan motors within manufacturer's tolerances. They are controlled by a
variable speed switch
• Mains cables and control circuit wires are to be connected as per wiring diagram
and all wiring must comply with relevant local wiring rules.
• Single phase fan motors are internally protected and there is no need for
external overload switches.
WM-ERV Manual 2005.2.doc2
6