Baumer NE230 Instrukcja obsługi - Strona 28

Przeglądaj online lub pobierz pdf Instrukcja obsługi dla Licznik gotówki Baumer NE230. Baumer NE230 44 stron. Electronic preset counter in din rail housing

NE230
28
Litz contact only by means of connector sleeves with insulating
enclosures for reasons of shock protection according to EN 61010.
Do not otherwise assign contacts that have been left unassigned ex
factory. We recommend to screen all sensor terminal leads and to
ground the shield on one side. Shields on both sides are recommen-
ded in case of RF interference or in case of equipotential bonding
over long distances. The sensor leads should not be in the same
phase winding as the mains supply and the output contact leads.

3.1 Voltage supply connection

Three voltage ranges are available for the voltage supply.
AC voltage 85...265 VAC (50/60 Hz)
AC voltage 10...26 VAC (50/60 Hz)
DC voltage 10...30 VDC, 5% residual ripple
AC voltage connection:
Connect AC at the contacts 1 and 2 according to the counter termi-
nal diagram.
Voltage supply
85...265 VAC, 50/60 Hz
10...26 VAC, 50/60 Hz
DC voltage connection:
Connect an interference-free power supply, i.e. do not use the paral-
lel connection of the drive systems, contactors, solenoid valves, etc.
Connect the DC voltage in accordance with the counter wiring dia-
gram.
Voltage supply
10...30 VDC
Fire protection: Operate instrument on the MAINS with external fuse
recommended on the rating plate. In case of disturbance, make sure
that 8 A /150 VA (W) are never exceeded - as defined per EN 61010.
www.baumer.com
Recommended external fusing
M 315 mA
M 400 mA
Recommended external fusing
M 400 mA