Atkinson Electronics GSCM Instrukcja obsługi i instalacji - Strona 11
Przeglądaj online lub pobierz pdf Instrukcja obsługi i instalacji dla Jednostka sterująca Atkinson Electronics GSCM. Atkinson Electronics GSCM 16 stron. Generator start control module
Również dla Atkinson Electronics GSCM: Podręcznik (16 strony)
GENERATOR START CONTROL MODULE
GSCM
APPLICATION 4 - DIESEL GENERATORS
The diesel generator is started by the GSCM in either automatic or manual mode. A field installed relay that will handle the glow
plug current is needed if not already installed on the engine. A fuel control solenoid is connected to the K3 (ignition) relay
terminals. A decompression solenoid furnished with the generator must be wired to K4 (shutdown) relay to energize on shutdown.
APPLICATION 5 - AUTOMATIC GENERATOR POWERED AC PUMP
In this application the GSCM is connected to a pressure or level switch into the battery sense terminals. See Section-3:9 for
making the appropriate cut-in and cut-out adjustments. The cut-in and cut-out adjustments must be set at the maximum for the
switched input auto start mode to operate (see Sections 3:9 & 4:9). The K5 (load) relay energizes the pump contactor.
ATKINSON ELECTRONICS, INC.
REV 8/06
Web Site: www.atkinsonelectronics.com
Distributed by: