3) Connecting the device
- The device must be supplied with 230V, 50Hz.
- Mains connection must be ensured using a 3-wire cable
(Brown=Phase, Blue=Neutral, Black=Pilot wire), through
a connecting box. In damp premises, such as bathrooms
and kitchens, install the connecting box at least 25cm
from the ground.
- The installation must be equipped with a shutting-off devi-
ce in all poles having a distance of opening of contact of
at least 3mm.
- Ground connection is forbidden.
Do not connect the pilot wire (black) to ground.
- If power cable is damaged or too short, to avoid any danger it must be replaced by a qualified electrician
using special tools.
- If a device pilots or is piloted by a 30mA differential (e.g. bathroom), the pilot wire supply must be pro-
tected on this differential.
4) How to connect the mixed version to the water system ?
For the connection of hot water, the mixed version comprises 2 threaded ports 1/2 gas 15/21 F situated at
the base, as well as a purge with adjustable spray on the top on the right
Follow the flow direction as well as the figures stipulated on the diagram below.
WALL
CONNECTION
GROUND
CONNECTION
SIDE VIEW
Threaded ports
1/2 GAS 15/21 F
115
mini
122 maxi
Panel heater cable
Phase=brown
Neutral=blue
Pilot wire=Black
Two possible cases
1st case: only one heater
2nd case: multiple heaters
MIDDLE OF THE DEVICE
386
WATER INLET
1/2 GAS 15/21 F
446
FRONT VIEW
PHASE
Electricity
grid
NEUTRAL
The pilot wire end is insulated
and not further connected
The pilot wire of all heaters in a
control group, up to a maximum
of 20 units with any one them used
as the Master, are connected
by a 1.0mm2 220-240V insulated cable
80
COVER
WATER OUTLET
1/2 GAS 15/21 F
195