Absolute Process Instruments API 1040 G A230 Skrócona instrukcja obsługi

Przeglądaj online lub pobierz pdf Skrócona instrukcja obsługi dla System bezpieczeństwa Absolute Process Instruments API 1040 G A230. Absolute Process Instruments API 1040 G A230 2 stron. Dc input alarm trips with transmitter and loop supply

DC Input Alarm Trips with Transmitter and Loop Supply
Input:
0-100 mV to 200 VDC, 0-1 mA to 0-50 mADC, 4-20 mADC
Outputs:
One 8 Amp SPDT Relay, 0-1 V to ±10 VDC, 0-2 mA to 0-20 mADC
O DC Input with Loop Supply
O Field Adjustable Setpoints
O Plug-In Design for Fast Installation
O Input LoopTracker
®
and Alarm Status LEDs
O Alarm Test, Optional Reset Button
O Optional 0-1 V Setpoint Retransmission Output
Applications
Q Process Signal Retransmission with Alarm
Q Alarm and Rescale a Process Signal
DC Input Range
Factory configured, please specify input range
Voltage:
0-100 mVDC to 0-200 VDC
Bipolar voltage: ±100 mVDC to ±10 VDC
Current:
0-1 mADC to 0-50 mADC
Input Impedance and Burden
Voltage:
250 kΩ minimum
50 Ω typical (1 VDC burden at 20 mA)
Current:
Isolation and Input Protection
750 VAC
or 750 VDC common mode protection
p
Input isolated from power supply
Input Loop Power Supply
18 VDC unregulated, 25 mADC, <1.5 V
p-p
May be selectively wired for sinking or sourcing mA input
LoopTracker
Variable brightness LED indicates input loop level and status
DC Output Range
Factory configured, please specify output range
Voltage: 0 to 1 VDC to ±10 VDC
Current: 0 to 2 mA to 0 to 20 mA
20 V compliance, 1000 Ω at 20 mA
Output Calibration
Multi-turn zero and span potentiometers, ±15% of span typ.
Relay Output
One SPDT form C contact set
Factory configured alarm type
Standard: HI alarm, non-latching, normal acting
Options: LO alarm, latching, reverse acting
Relay Contact Rating
8 A @ 240 VAC resistive load or 30 VDC resistive load
5 A @ 240 VAC inductive load (cos f = 0.4)
3.5 A @ 30 VDC inductive load (L/R = 7ms)
Caution: Do not exceed socket voltage rating
Use an RC snubber for inductive loads
Setpoint
One 12 turn potentiometer, 0-100% of span
SPR option: 0-1 V output of alarm setpoint
Deadband
1.0 to 100% of span, 12 turn potentiometer
Alarm trip/reset window is symmetrical about the setpoint
Output Test/Reset Button
Test button toggles relay to opposite state when pressed
HT option: Reset button resets latching relay
Accuracy
±0.1% of span (includes adjustment resolution and linearity)
Response Time
70 milliseconds typical
Ambient Temperature Range and Stability
–10°C to +60°C operating ambient
Better than 0.02% of span per °C stability
Housing and Sockets
IP 40, requires installation in panel or enclosure
API 011 or API 011 FS socket
Socket mounts to 35 mm DIN rail or can be surface mounted
Power
Standard:
115 VAC ±10%, 50/60 Hz, 2.5 W max.
P option:
85-265 VAC 50/60 Hz, 60-300 VDC, 2.5 W typ.
A230 option: 230 VAC ±10%, 50/60 Hz, 2.5 W max.
D option:
9-30 VDC, 2.5 W typical
BSOLUTE
Deadband Adjustment
Variable Brightness Input LED
Output Test Button
Output Span
Output Zero
Reset Button with HT Option
Setpoint Adjustment
Bi-Color Relay LED
Variable Brightness Output LED
0.5
0.3
0.1
ripple
Description
The API 1040 G alarm/transmitter accepts a DC voltage or
current input and provides both transmitter and alarm func-
tions in one unit.
The API 1040 G also provides a linearly-transferred DC voltage
or current output. The API 1040 G transmitter output is useful
for signal scaling, or translation from current to voltage or vice-
versa in applications that do not require isolation.
This module includes an unregulated 18 VDC loop excitation
supply that can be used to power an external loop-powered
transmitter or other passive input device eliminating the need
for an additional DC loop supply.
The API 1040 G provides a visual alarm indication and an SPDT
alarm relay output when the input exceeds a high alarm trip
point or falls below a low alarm trip point.
The alarm output can be factory configured for HI or LO opera-
tion, non-latching or latching, normal or reverse acting. Top-
accessible potentiometers are used to adjust the alarm setpoint
and deadband. Heavy-duty relay contacts allow the module to
directly control high capacity loads.
Model
API 1040 G
API 1040 G A230
API 1040 G P
API 1040 G D
API 1040 G SPR
API 1040 G A230 SPR
API 1040 G P SPR
API 1040 G D SPR
Options—add to end of model number
L
LO trip. Alarm trips on decreasing signal.
HT Latching alarm with push button reset
HP Latching alarm with power-off reset
Module power must be turned off to reset alarm
R
Reverse-acting alarms. Relay coils energized in an alarm
condition. No alarm condition with module power off.
U
Conformal coating for moisture resistance
Accessories—order as a separate line item
API 011
11-pin socket, DIN rail or surface mount
API 011 FS 11-pin finger safe socket, DIN rail or surface mount
API CLP1
Module hold-down spring for high vibration or
mobile applications
ROCESS NSTRUMENTS, Inc.
1.75"
AC inductive load
AC resistive
(cos f = 0.4)
load
8
5
3
DC inductive load
1
(L/R = 7 ms)
DC resistive
load
0
3 5 10
30 50 100 300 500
Switching Voltage (V)
Relay Contact Ratings
Input
Factory ranged; specify mV, V, or mA range.
Factory ranged; specify
One SPDT relay, HI alarm, normal acting.
mV, V, or mA range
Specify alternate alarm configurations and options
Factory ranged; specify mV, V, or mA range.
Factory ranged; specify
One SPDT relay, HI alarm, normal acting.
mV, V, or mA range
Specify alternate alarm configurations and options
1220 American Way Libertyville, IL 60048
800-942-0315
Phone:
2.38"
Quick Link
api-usa.com/1040
Setpoint Retransmission Option
The setpoint retransmission (SPR) option provides an analog
0-1 VDC signal corresponding to the setpoint potentiometer
adjustment. This allows remote monitoring of the alarm setting.
LoopTracker and Alarm Status LEDs
API exclusive features include a LoopTracker LED that varies in
intensity with changes in the process input signal.
A red/green bi-color alarm status LED visually indicate alarm
status. These LEDs provide a quick visual picture of your
process at all times.
Output Test/Unlatch
API's exclusive functional test button can be used to verify the
alarm and system operation. The output test button greatly
aids in saving time during initial startup and/or troubleshooting.
The HT latching option provides the additional function of
unlatching the alarm when the reset button is pressed. The
alarm will reset if the alarm condition not longer exists.
Output
0-1 V alarm setpoint retransmission.
API 011 FS
API 011
300 V Rating
300 V Rating
api-usa.com
Fax: 800-949-7502
API 1040 G
2.75"
Hot Swappable
Plug-In Design
H H H H H H
H H H H H
H H H H H H
H H H H H
H H H H H H
H H H H H
H H H H H H
H H H H H
H H H H H H
Made in USA
Free Factory
I/O Setup!
Power
115 VAC
230 VAC
85-265 VAC or 60-300 VDC
9-30 VDC
115 VAC
230 VAC
85-265 VAC or 60-300 VDC
9-30 VDC
API CLP1
© 08-15