[Notes on Combined Use of 4-Wire (Isolated) Terminal]
If the total length of the sections where all the DP, DN, 24V, and 0V lines
run in parallel in the power supply system is more than 50m, connect
an ASLINK filter (Type ANF-01) or a filter manufactured by COSEL Co.,
Ltd. (Type EAC-06-472) in series to the 24V and 0V lines at a position
where these four lines start running in parallel.
This will improve noise resistance, suppress the adverse effects of
crosstalk caused by transmitted signals, and stabilize signals.
The above filters must be inserted regardless of whether power is
supplied to all terminals collectively from the power supply for the
master or power is supplied to each terminal individually from their local
power supply.
Insert the "ASLINK filter [Type ANF-01]" regardless of installation
method and distance when complying with CE Standard.
■Filter allowable current
Product
ASLINK filter
Filter of COSEL Co., Ltd. EAC-06-472 MAX 6A/24V DC
■AnyWire Type: ANF-01 Connection example
(The drawing below is a connection diagram for the purpose of explanation. Actual
connection should be made in accordance with the terminal arrangement on each device.)
① Power supply to the entire system
AnyWireASLINK master
General-purpose power
supply filter
(Use it if necessary.)
0V
24V
24V DC stabilized
power supply
L N FG
~
If the total length of the section
where all the DP, DN, 24V, and 0V
lines run in parallel is more than 50m
Type
Allowable power current
ANF-01
MAX 5A/24V DC
DP
DN
24V
0V
LG
POWER IN
PE
0V
24V
ANF-01
0V
24V
SLAVE
DP
DN
DP
DN
24V
0V
Terminator
② Local power supply/branching
AnyWireASLINK master
General-purpose power
supply filter
(Use it if necessary.)
24V DC stabilized
power supply
If the total length of the section
where all the DP, DN, 24V, and 0V
lines run in parallel is more than 50m
~
A
If the total length of the sections
(A + B) where all the DP, DN, 24V,
and 0V lines run in parallel is more
than 50m
2-wire
terminal
4-wire
terminal
-BSK5217M**1K 3/9-
DP
DN
24V
0V
LG
POWER IN
PE
0V
ANF-01
0V
24V
0V
SLAVE
L N FG
~
24V DC
General-purpose power
stabilized
supply filter
power supply
(Use it if necessary.)
N
24V
L
0V
POWER IN
FG
PE
0V
ANF-01
0V
SLAVE
DP
4-wire
DN
24V
terminal
0V
B
DP
DN
4-wire
24V
terminal
0V
24V
24V
2-wire
DP
terminal
DN
DP
4-wire
DN
terminal
24V
0V
DP
4-wire
DN
24V
terminal
0V
2-wire
DP
terminal
DN
2-wire
DP
terminal
DN
24V
24V
DP
4-wire
DN
24V
terminal
0V
DP
DN
4-wire
24V
terminal
0V
DP
4-wire
DN
24V
terminal
0V
Terminator