■Alarm Hi setting
This parameter determines the upper limit for issuing an alarm.
- Address Writer (ARW-04, ARW-03): Parameter 03
Variable
Unit
0–100
%
Factory Setting: 80
*
Set the alarm level so that the relationship Hi > Lo will be satisfied.
■Alarm Lo setting
This parameter determines the lower limit for issuing an alarm.
- Address Writer (ARW-04, ARW-03): Parameter 04
Variable
Unit
Factory Setting: B S-K5217-M18-1K: 6
0–100
%
*
Set the alarm level so that the relationship Hi > Lo will be satisfied.
■Alarm monitoring time setting
This parameter determines the monitoring time of alarm determination.
- Address Writer (ARW-04, ARW-03): Parameter 05
Variable
Unit
3–255
100ms
Factory Setting: 50
■Normally open/Normally closed setting
This parameter determines the normally open or normally closed
operation of contacts.
- Address Writer (ARW-04, ARW-03): Parameter 06
Variable
Description
ON with a workpiece
0
Normally open
ON without a workpiece
1
Normally closed
■Alarm diagnosis setting
This parameter enables or disables the alarm diagnosis feature.
- Address Writer (ARW-04, ARW-03): Parameter 07
Variable
Description
0
OFF
Alarm diagnosis disabled
Alarm diagnosis enabled
1
ON
■Delay timer ON/OFF setting
This parameter sets up the ON delay and OFF delay timers.
- Address Writer (ARW-04, ARW-03): Parameter 10
Variable
Description
0
Without delay timer
Delay timer disabled
1
ON delay timer
ON delay timer enabled
2
OFF delay timer
OFF delay timer enabled
3
ON/OFF delay timer
ON/OFF delay timer enabled
■Delay setting
Once a delay timer has been enabled with Parameter 10, it is
possible to set up the delay.
- Address Writer (ARW-04, ARW-03): Parameter 11
Variable
Unit
10ms
0–255
Factory Setting: 0
Parameters 08, 09 and 12 through 19 are
CAUTION
values relevant to the internal setting. Do not
modify these values.
BS-K5217-M30-1K: 7
Factory Setting: 0
Factory Setting: 0
Factory Setting: 0
-BSK5217M**1K 7/9-
[Monitor Display]
The operation status of ASLINKSENSOR is displayed by LED indicators.
Normal condition: LINK flashing, ALM unlit and IN ON (lit) or
OFF (unlit)
Display status
LED name
Lit
LINK
Flashing
(Green)
Unlit
Lit
Flashing
(Lit for 0.2 sec, unlit for 1.0 sec)
ALM
(Red)
Flashing
(alternates with a 0.1 sec interval)
Unlit
Alternate flashing
LINK
LINK
ALM
ALM
Lit
IN
(Orange)
Unlit
Description
Transmission signal error
Transmission signal supplied properly
No transmission signal
Sensing level drop
*
Slave unit voltage drop
Teaching error
Normal
The master unit has detected that the
unit ID (address) is either duplicated or
unregistered
ON
OFF
*
Only if the alarm diagnosis feature is enabled
LINK (Green)
IN (Orange)
ALM (Red)