AutomationDirect ProSense SC6-1100 Skrócona instrukcja obsługi

Przeglądaj online lub pobierz pdf Skrócona instrukcja obsługi dla Konwerter mediów AutomationDirect ProSense SC6-1100. AutomationDirect ProSense SC6-1100 2 stron. Signal conditioners

AutomationDirect ProSense SC6-1100 Skrócona instrukcja obsługi
SC6 Series Signal Conditioners
Quick Start Guide
Description:
This Quick Start Guide provides basic information for configuring the ProSense SC6 series signal condi-
tioners. For more specific information and additional instructions please visit www.AutomationDirect.
com and download the free instructions manuals for the SC6 series.
~ WARNING ~
To avoid the risk of electric shock and fire, the safety instructions of this guide must be observed
and the guidelines followed. The specifications must not be exceeded, and the device must only be
applied as described in the following. Prior to the commissioning of the device, this installation guide must
be examined carefully. Only qualified personnel (technicians) should install this device. If the equipment
is used in a manner not specified by the manufacturer, the protection provided by the equipment may be
impaired. Until the device is installed, do not connect hazardous voltages to the device.
In applications where hazardous voltage is connected to in /outputs of the device, sufficient spacing
or isolation from wires, terminals and enclosure to surroundings (incl. neighboring devices), must be
ensured to maintain protection against electric shock.
Potential electrostatic charging hazard. To avoid the risk of explosion due to electrostatic charging
of the enclosure, do not handle the units unless the area is known to be safe, or appropriate safety
measures are taken to avoid electrostatic discharge.
SAFETY INSTRUCTIONS
Receipt and unpacking
Unpack the device without damaging it. The packing should always follow the device until it has been
permanently mounted. Check at the receipt of the device whether the type corresponds to the one ordered.
Environment
Avoid direct sunlight, dust, high temperatures, mechanical vibrations and shock, as well as rain and heavy
moisture. If necessary, heating in excess of the stated limits for ambient temperatures should be avoided
by way of ventilation. All devices can be used for Measurement / Overvoltage Category II and Pollution
Degree 2. The module is designed to operate safely at an altitude of 2000m or less.
Mounting
Mounting and connection of the device should comply with national legislation for mounting of electric
materials, i.e. wire cross section, protective fuse, and location. Descriptions of input / output and supply
connections are shown in this installation guide and on the side label.
The device is provided with field wiring terminals and shall be supplied from a power supply having
double or reinforced insulation. A power switch should be easily accessible and close to the device. The
power switch shall be marked as the disconnecting unit for the device.
The SC6 Series must be mounted on a DIN rail that complies with EN 60715.
UL installation
Use 60/75°C copper conductors only.
Wire size ...................................... AWG 26-12
UL file number............................. E498965
The device is an Open Type Listed Process Control Equipment. To prevent injury resulting from access-
ability to live parts the equipment must be installed in an enclosure.
The Division 2 or Zone 2 power supply unit must comply with NEC Class 2, as described by the National
Electrical Code® (ANSI / NFPA 70).
cFMus installation in Division 2 or Zone 2
FM18US0045X ......................... Cl. I, Div. 2, Group A, B, C, D T4
or Cl. I, Zone 2, AEx nA IIC T4
FM18CA0023X ......................... Cl. I, Div. 2, Group A, B, C, D T4
or Cl. I, Zone 2, Ex nA IIC T4
In class I, Division 2 or Zone 2 installations, the subject equipment shall be mounted within a tool secured
enclosure which is capable of accepting one or more of Class I, Division 2 wiring methods specified in the
National Electrical Code (ANSI/NFPA 70) or in Canada in the Canadian Electrical Code (C22.1).
The SC6 Series Isolators and Converters must be connected to limited output NEC Class 2 circuits, as
outlined in the National Electrical Code® (ANSI / NFPA 70), only. If the devices are connected to a
redundant power supply (two separate power supplies), both must meet this requirement.
Where installed in outdoor or potentially wet locations the enclosure shall at a minimum meet the require-
ments of IP54.
Warning: Substitution of components may impair suitability for zone 2 / division 2.
Warning: To prevent ignition of explosive atmospheres, disconnect power before servicing and do not
separate connectors when energized and an explosive gas mixture is present.
Warning: Do not mount or remove devices from the power rail when an explosive gas mixture is present.
Cleaning
When disconnected, the device may be cleaned with a cloth moistened with distilled water.
3505 HUTCHINSON ROAD
CUMMING, GA 30040-5860
Copyright 2019, Automationdirect.com™
Incorporated All Rights Reserved
Technical Specifications
Operating temperature .............................. - 25°C to +70°C (-13°F to 158°F)
Storage temperature .................................. -40°C to +85°C (-40°F to 185°F)
Supply voltage........ ................................... 16.8...31.2 VDC
Supply voltage, SC6-6102 ......................... Loop -powered / 3.3...35 VDC
Supply voltage, SC6-7102 ......................... Loop -powered / 5.5...35 VDC
Supply voltage, SC6-1101, -1111............... ≤ 1.25 V + (0.015 x Voutput)
Supply voltage, SC6-4102, -4112, -1102, -1112..... Loop -powered /
Max. required power:
SC6-5200, -6200........................................ 0.7 W
SC-1100, -1110, -3200, -7102, -6102........ 0.8 W
SC6-2200, -2220, -3220............................. 1.2 W
SC6-1101, -1111........................................ 30mW per channel
SC6-4102, -4112........................................ 50mW per channel
SC6-1102, -1112 ....................................... Vterminal x I per channel
¹Isolation voltage, test ................................. 2.5 kVAC
¹Isolation voltage, working .......................... 300VAC (reinforced) /
Double isolation.......................................... Input/output 1/output 2/supply
Relative humidity........................................ < 95% RH (non-cond.)
Dimensions (HxWxD) ............................... 113 x 6.1 x 115 mm
Protection degree ........................................ IP20
Weight ....................................................... 70 g
Approvals
UL, Standard for Safety .............................. UL 61010 -1
Safe isolation .............................................. EN 61140
cFM us........................................................ Zone 2 / Div. 2
Observed authority requirements:
EMC ........................................................... 2014/30/EU
LVD ............................................................ 2014/35/EU
RoHS 2........................................................ 2011/65/EU
¹Does not apply to SC6-6102
Installation:
This installation guide for technical personnel covers the following products:
SC6-1100
SC6-1110
SC6-2200
SC6-3220
SC6-1101
SC6-1111
SC6-2220
SC6-4102
SC6-1102
SC6-1112
SC6-3200
SC6-4112
Installation on DIN rail:
To avoid short circuit between the power rail connectors on the
SC6 Series devices and the screws holding the 7.5 mm DIN rail,
the head of the screws shall be no more than 3.5 mm high. SC6
Series units must be supported by module stops (ADC Series
KN-EB7).
35 mm
> 24 mm
Demounting from DIN rail:
First, remember to demount the connectors with hazardous volt-
ages. Detach the device from the DIN rail by lifting the bottom
lock.
Wire size AWG 26...12 / 0.13...2.5 mm2 stranded wire. Screw
terminal torque 0.5 Nm.
Supply of the Power rail:
The power rail can be powered via the SC6-PCU1 Power Connector unit or alter-
natively a SC6 series unit with power rail connector power terminals. Max. current
values are to be observed:
SC6 Series unit with power rail connector ......................0.4 A (protective fuse 0.4 A)
SC6-PCU1 unit..............................................................2.5 A (protective fuse 2.5 A)
Required external fuse:
Supply directly on device.................................................2.5 A
Supply of power rail using a standard device....................0.4 A
SC6-PCU1 Power connect unit.......................................2.5 A
Fuse Characteristics:
The 2.5 A fuse must break after not more than 120 seconds at 6.4 A.
Side Label
Terminal numbers
AutomationDirect
3505 Hutchinson Road
Cumming, GA 30040
800-633-0405
www.automationdirect.com
Part number
}
DIP-switch
settings
6.0...35 VDC
250VAC (Zone 2, Div. 2)
SC6-5200
SC6-7102
SC6-6102
SC6-PCU1
SC6-6200
< 3.5 mm
}
Pin
}
connections
Approvals