Automationdirect.com Productivity 1000 P1-4ADL2DAL-2 Podręcznik
Przeglądaj online lub pobierz pdf Podręcznik dla Systemy wejścia/wyjścia Automationdirect.com Productivity 1000 P1-4ADL2DAL-2. Automationdirect.com Productivity 1000 P1-4ADL2DAL-2 8 stron. Analog input/output
General Specifications
Operating Temperature
Storage Temperature
Humidity
Environmental Air
Vibration
Shock
Field to Logic Side
Isolation
Insulation Resistance
Heat Dissipation
Enclosure Type
Module Location
Field Wiring
EU Directive
Terminal Type
(sold separately)
Weight
Agency Approvals
*See CE Declaration of Conformance for details.
Sales 800-633-0405
0º to 60ºC (32º to 140ºF)
-20º to 70ºC (-4º to 158ºF)
5 to 95% (non-condensing)
No corrosive gases permitted
IEC60068-2-6 (Test Fc)
IEC60068-2-27 (Test Ea)
1800VAC applied for 1 second
> 10M: @ 500VDC
1950mW
Open Equipment
Any I/O position in a Productivity1000 System
Removable terminal block (sold separately). Use
ZIPLink Wiring System optional See "Wiring
Options" on page 5.
See the "EU Directive" topic in the Productivity
Suite Help File. Information can also be obtained at:
www.productivity1000.com
10-position Removable Terminal Block
60g (2.1 oz)
UL 61010-1 and UL 61010-2-201 File E139594,
Canada and USA
CE (EN 61131-2 EMC, EN 61010-1 and EN 61010-
2-201 Safety)*
P1-4ADL2DAL-2 Analog Input/
Output
P1-4ADL2DAL-2
The P1-4ADL2DAL-2 Voltage Analog Input/Output
Module provides four 13 bit input channels at 0-10
VDC and two 12 bit output channels at 0-10VDC for
use with the Productivity1000 system.
General Specifications . . . . . . . . . . . . . . . . . . . . . . 1
Input Specifications . . . . . . . . . . . . . . . . . . . . . . . . . 2
Output Specifications . . . . . . . . . . . . . . . . . . . . . . . 2
Wiring Diagram and Schematic . . . . . . . . . . . . . . . . 3
Module Installation Procedure . . . . . . . . . . . . . . . . . 4
24V
QR Code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Wiring Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
V1+
Module Configuration . . . . . . . . . . . . . . . . . . . . . . . 5
V2+
Linear Scaling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Non-Linear Scaling . . . . . . . . . . . . . . . . . . . . . . . . . 6
V3+
Warning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Terminal Block Specifications . . . . . . . . . . . . . . . . . 8
V4+
0V
V1+
V2+
COM
COM
0-10VDC IN
Terminal Block sold separately, (see wiring options on page 5).
0-10VDC OUT
Warranty: Thirty-day money-back guarantee. Two-year limited
replacement. (See www.productivity1000.com for details).
www.productivity1000.com
1000
1