Create a closed drying chamber
The dehumidifier should be operated in an enclosed space in order to create a
drying chamber. Close all doors, windows or areas that open to the outside to
maximize the unit's water removal efficiency. Inside the drying chamber, air
should circulate freely. Open interior doors and turn on Air Movers to increase
the circulation.
Position the dehumidifier
Place the dehumidifier in the center of a room and keep it away from anything
that could prevent airflow into and out of the unit.
Managing the rising temperature
The dehumidifier warms the air as it removes moisture. Room temperatures
o
o
between 68
F and 84
F are favorable temperatures for drying. In summer
months while drying flooded homes, set the A/C to 68
constant (ON). This will circulate the air in the entire home to make sure the
dry air is distributed evenly. In the winter, set the furnace to at least 65
the blower set to the "ON" position.
When the unit has been stored or transported in temperatures below 60
place the dehumidifier in the room for about an hour before operating (when
possible). This will allow the unit to acclimate to the warmer ambient
temperature minimizing conditions that cause the coils to freeze up thereby
engaging the defrost cycle.
CAUTION! Never operate the Aquatrap dehumidifier at temperatures above
o
100
F. It could damage the machine construction and internal
components.
o
F with the A/C blower on
o
F with
o
F,
Error Messages
Message
Icon
Description
Er01
"PUMP ON"
Problem with pump or the drain tube is kinked.
flashing
Er02
N/A
Check coil temperature sensor at the side of coil and
the sensor cable.
Er03
N/A
Check ambient temperature sensor in the front of the
coil and the sensor cable.
Note:.
When Er01 or Er02 error message displays, the dehumidification cycle will stop
automatically. The machine will revert to STANDBY MODE but will still be on
unless manually turned off. Contact Abatement Technologies for service.
When Er03 error message displays, the dehumidification cycle is still on. Contact
Abatement Technologies for service.
Indication Light:
Status
Colors
Description
Off
Machine is off.
N/A
On
Red
Machine is on.
On
Green
Machine dehumidification cycle is on.
Maintenance
WARNING! Always unplug any dehumidifier before performing maintenance
procedures.
Before Each Use
Inspect the electrical cord for damage.
Inspect condensate pump drain tube. Make sure the drain tube is
completely unwrapped and not kinked. Failure to do so can cause water
to back up in the pump and leak out. The control panel may signal this
problem by displaying "ER01