Accutrol HSS1 Series Skrócona instrukcja obsługi
Przeglądaj online lub pobierz pdf Skrócona instrukcja obsługi dla Systemy kontroli Accutrol HSS1 Series. Accutrol HSS1 Series 2 stron. Fume hood control system
Quick Start Guide
AVC6 Fume Hood Control System
This Quick Start Guide provides the basic steps required for the
installation, wiring and start-up of the AVC6 Fume Hood Control
System. For details, refer to the individual product Submittal
Drawings, User Manuals and Job-Specific Requirements.
APPLICATION
The AVC6 Fume Hood Control System is comprised of the
®
award-winning AccuValve
dedicated Fume Hood Controller Display Module, Model FHM3.
For VAV applications sash sensors are provided for precise
measurement of the fume hood face open area.
applications sash switches can be used to change the airflow
volume set point to achieve energy savings.
diagram shows the main components of the AVC6 Fume Hood
Control System.
AccuValve®
Model AVC6000
Sash Sensor
Model VSS-50
STEP 1: INSTALLATION
CAUTION: Wear eye protection, cut resistant
gloves and clothing suitable for working with
sheet metal. Failure to do so may result in
personal injury.
1a. Install AVC6 AccuValve
Select a location in close proximity to the fume
hood and install the valve per the AVC6 Submittal
Drawing and Manual.
Verify the Airflow Direction Label located on the
valve is positioned in agreement with the exhaust
airflow direction of the duct and the controller is
accessible for wiring.
www.accutrolllc.com or www.AccuValve.com
, Model AVC6, paired with a
For CAV
The following
Fume Hood Monitor
Model FHM3
Models: AVC6, FHM3, VSS-50 and HSS1-xx
1b. Install FHM3 Module
Install the FHM3 into a single-
gang electrical box located on
the front of the fume hood. Be
sure to select a location that
provides unobstructed access
for the user and is clearly
visible so the display can be
easily viewed.
If the fume hood does
not have a preinstalled
electrical box available,
then one will need to be
installed.
1c. Install Sash Sensors
Vertical Sash Sensor (VSS): Select a suitable location to attach
the retractable cable to the fume hood sash or counterweight
system per the VSS-50 Installation Drawing.
CAUTION: Do not allow the wire rope to "snap back" into the
reel or damage to the part or personal injury can result.
After securing the VSS to the fume hood and attaching the
retractable cable, verify operation by slowly raising and lowering
the sash while observing the VSS and retractable cable to ensure
the wire rope extends and retracts straight and without
interference.
Horizontal Sash Sensor System: Install the Panel Magnets and
HSS onto the fume hood per the instructions provided in the
Manual. Use the HSSK Horizontal Sash Kit to manage the cables
to prevent them from getting damaged. Due to variations in fume
hood construction, custom brackets may be required.
STEP 2: WIRING
Connections to the AVC6 Control Module will vary depending on
the application requirements. The below diagram is provided as a
general reference only. For detailed wiring requirements, refer to
the job specific submittal wiring diagrams and AVC6 Manual.
1
AVC6 FUME HOOD CONTROL SYSTEM QUICK START GUIDE— MAY 2019