ActronAir ERQ5-21AS Podręcznik instalacji i uruchomienia - Strona 4
Przeglądaj online lub pobierz pdf Podręcznik instalacji i uruchomienia dla Akcesoria do klimatyzatorów ActronAir ERQ5-21AS. ActronAir ERQ5-21AS 20 stron. Esp platinum que split ducted unit - 3 phase
Installation and Commissioning Guide
02. Safety Instructions
● Only licensed HVAC technicians* should install and service this air conditioning equipment. Improper service or
alteration by an unqualified technician could result in significant and major damage to the product or property
which may render your warranty null and void. Such unqualified service could also lead to severe physical injury or
death. Follow all safety instructions in this literature and all warning labels that are attached to the equipment.
● Prevailing WH&S regulations must be observed and will take precedence to the safety instructions contained on
this manual. Safe work practices and environment must be the paramount importance in the performance of all the
service procedures.
● Ensure that unit installation complies with relevant council regulations and building code standards.
● All electrical wiring must be in accordance with current electrical authority regulations and all wiring connections to
be as per electrical diagram provided.
● Secure the fans against accidental contact. Beware of pinch point and sharp edges which can cause cutting injury.
● Always wear appropriate PPE, remove any dangling jewellery and protect long hair by wearing a cap.
● Make sure that safety guards and panel covers are always firmly secured and not damaged.
● This appliance is not intended for use by young children or infirm persons unless they have been adequately
supervised by a responsible person to ensure that they can use the appliance safely. Young children should be
supervised to ensure that they do not play with the appliance.
● Installer must incorporate a means of electrical disconnection (isolator) in the sub mains fixed wiring in accordance
with AS/NZS 3000:2018 (also known as Australian Wiring Rules).
● Secure the power cords and control cables that goes in/out the unit. Use the cable ties provided in the control box.
*Qualifications required will be appropriate Electrical, Refrigeration and Refrigerant Handling License and
Training dependent on local State/Territory regulations.
IMPORTANT NOTES TO INSTALLER
• This indoor unit is designed to match only with a specific ActronAir outdoor unit as specified in the Technical Selection
Catalogue.
• This unit is designed for use with R410A refrigerant only.
• The unit is supplied with factory charged dry air. Beware of the pressurised air charge when purging. Remove the caps from
the connection points and purge the system only when the field pipe connections are ready to be completed.
DANGER
Hazardous Voltage - Risk of Electrocution.
TURN-OFF the power from main isolator before proceeding with any service work of the unit. Observe proper LOCK-OUT/TAG-
OUT (LOTO) procedures for electrical appliances in order to prevent accidental switching-on of the power supply.
WARNING
EC Motors and Inverter Drives are fitted with high power capacitors and can have dangerous residual voltages at motor terminals
after power has been isolated. Wait at least 5 minutes after power isolation and test for any residual voltage before beginning
service work.
VISUAL INSPECTION AND WORK ASSESSMENT
Work areas and conditions must first be assessed and evaluated for any potential hazardous conditions. It is also important to be
familiar with the unit parts and components before proceeding with any service task.
04
Installation & Commissioning Guide - ESP Platinum QUE Split Ducted Units
Doc. No.0525-061 Ver. 1 190131
ESP Platinum QUE - Three Phase