If you do wiring in conduits, see the drive hardware manual for more information.
DC/
MCB/
1
Fuse
1.
Reverse polarity diodes.
2.
EMI filter is optional but is mandatory for IEC/EN62920 standard compliance which is required in Europe.
3.
Ground connection should be common for MOV, drive, and pump.
Note: ACQ80-01 drive is intended to be used for speed control of 3-phase AC pump motors and is powered from either AC
Grid or DC photo-voltaic array. ABB recommends not to use it as an island grid forming inverter or to supply generic single
phase or 3-phase loads, other than the 3-phase AC pump motors.

Connection procedure

1.
Frames R5: Remove the shroud(s) on the power cable terminals.
R5
1
2.
Prepare the power cables:
Remove the rubber grommets from the cable entry.
Cut a sufficient hole in the rubber grommet. Slide the grommet onto the cable (a).
Prepare the ends of the input power cable and motor cable as illustrated in the figure (b).
Slide the cables through the holes in the cable entry and attach the grommets to the holes.
If you use aluminum cables, apply grease to the stripped conductors before you connect them to the drive.
2a
AC grid or
generator
AC MCB/
MPCB
L2 L3
L1
MOV
DC+
EMI
ACQ80-01
3
filter
drive
MOV
DC-
2
PE
3
Earth pit 1
Earth pit 1
2b
PE
U
Pump
V
motor
W
Earth pit 1
3
5