ABB COM600 series Instrukcja obsługi produktu - Strona 14

Przeglądaj online lub pobierz pdf Instrukcja obsługi produktu dla Jednostka sterująca ABB COM600 series. ABB COM600 series 20 stron. Automation platform

ABB COM600 series Instrukcja obsługi produktu
Station Automation
COM600
Product version: 3.4
Table 11. Environmental tests
Description
Dry heat test
Cold test
Damp heat test, cyclic
Storage test
Table 12. Mechanical tests
Description
Vibration tests
• Vibration response test
• Vibration endurance test
Shock and bump tests
• Shock response test
• Shock withstand test
• Bump test
14
1MRS756764 B
Standard
According to IEC 60068-2-2
Test values:
• 96 h at +55ºC
• 4 h at +70ºC
According to IEC 60068-2-1
Test values:
• 96 h at -10ºC
• 4 h at -25ºC
According to IEC 60068-2-30
Test values:
• 6 cycles (12+12h) at
+25...55°C, humidity >93%
According to IEC 60068-2-48
Test values:
• 72 h at +70ºC
• 72 h at -40ºC
Standard
According to IEC 60068-2-6 and
IEC 60255-21-1
f = 10...150 Hz, ± 0.035 mm,
10...58 Hz,
5 m/s2 58...150 Hz
f = 10...150 Hz, ± 0.075 mm,
10...58 Hz, 10 m/s2 58...150
Hz
According to IEC 60068-2-27 ,
IEC 60068-2-29 and IEC 60255-
21-2
peak acceleration = 5 x gn,
pulse duration = 11 ms, num-
bers of pulses in each diretion
= 3
peak acceleration = 15 x
gn, pulse duration = 11 ms,
number of pulses in each direc-
tion = 3
peak acceleration = 10 x
gn, pulse duration = 16 ms,
number of pulses in each direc-
tion = 1000
ABB