Heat Recovery ventilation
Dee Fly Cube 550
INSTALLATION
The constant airflow or pressure kit features a ring to be positioned on air ducts; the pressurised air intakes must always be oriented
downwards to prevent the introduction of dust or foreign bodies into the system, as they could cause it to malfunction.
CONSTANT PRESSURE
The kit should be fitted on the exhaust air side (A) of the supply fan
unit to detect the pressure downstream.
Example of assembly of constant pressure kit
Supply air (indoor)
Expulsion air (outdoor)
Exhaust air (indoor)
Fresh air (outdoor)
Positioning of pre-heating coil
Supply air (indoor)
Expulsion air (outdoor)
Exhaust air (indoor)
Fresh air (outdoor)
Electrical connections:
• Minimum cable cross-section: 3 x 1.5 mm
• Power supply: 230 V single-phase.
A
2
.
CONSTANT AIRFLOW
The kit should be fitted on the exhaust air side (A) upstream of the fan
unit to detect the differential pressure without risking the falsification
of measurements by turbulence.
If two kits are required, the other should be fitted on the fresh air side
(B).
Example of assembly of constant airflow kit
B
Supply air (indoor)
Expulsion air (outdoor)
Exhaust air (indoor)
Fresh air (outdoor)
Connection of pre-heating coil
The pre-heating coil must be attached horizontally.
A