artisan Altivar 16 Series Podręcznik użytkownika - Strona 13

Przeglądaj online lub pobierz pdf Podręcznik użytkownika dla Kontroler artisan Altivar 16 Series. artisan Altivar 16 Series 17 stron. Speed controller for asynchronous motors

artisan Altivar 16 Series Podręcznik użytkownika

Motor thermal protection

Motor thermal protection is provided :
2
.
- by I
t thermal protection of the speed controller if the rated current of the motor is equal to
0.9 times the rated current of the speed controller for use in a frequency range from 25/30 to
50/60 Hz,
- or by using a thermal probe built into the motor, if used with high torque at low speed.

Available torque

Continuous operation :
For self-ventilated motors, motor cooling is linked to speed.
Derating occurs at speeds of less than half rated speed.
For fractional power motors of ≤ 250 W, derating may be less
(for example : 20 % instead of 50 % at very low frequency).
Transient operation :
The possibility of overtorque depends on the maximum transient current which the
speed controller can provide.
(50 Hz)
(60 Hz)
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Typical torque characteristics
Torque
C/Cn
1.50
1.25
1
2
0.75
0.50
0.25
0
5Hz
0
6Hz
3
1
25
50
30
60
1
Self-ventilated motor
2
Force-ventilated motor
3
Transient overtorque
Frequency (Hz)
E
N
G
L
I
S
H
23