STEP 5 Remove the cable grip nut from the plastic bag and put it on the other end of the cable
with the threads facing out. Remove 6 inches of the outer cover and strip back 3/8 inch
from each of the 7 wires.
STEP 6 Remove the 6 logic box cover screws and set the logic box cover aside. Thread the 7
wires through the upper or lower control hole in the logic box (see component layout,
Figure 5). Thread the cable grip washer and cable grip nut with the threads facing the box
on the cable. Pull enough cable through the cable grip to ensure a good fit. Tighten the
cable grip nut and attach the individual wires to the proper terminals (see wiring diagram
Figure 6). Reattach the logic box cover and secure with the 6 screws.
NOTE: The lower control and upper control wires must be attached to the correct
terminals for the lower control to override the upper control. The one attached to the
Master terminal will have the overriding capabilities.
Adjust the DIP switch settings as needed. (Refer to the description below.)
B. DIP SWITCH SETTINGS
The DIP switches are located in the logic box on the circuit board.
The switches are factory set at:
1
2
On
•
•
Off
Switch 1 - Allows the ability to use a 6-conductor controller for the Stow controller instead of 10-
conductor.
ON - Enables the 6-wire Stow controller
OFF - Disable the 6-wire Stow controller
Switch 2 - Allows the Stow and Deploy switch to be a momentary or a maintain switch.
ON - Requires JOG (maintain) to Stow or Deploy (No Learn mode if DIP 2 is ON)
OFF - Momentary switch to start the Stow or Deploy sequence (factory set)
Switch 3 - Lowers the monitor during the Deploy sequence for 2.5 seconds.
ON - Deploys for 2.5 seconds (factory set)
OFF - Will not Deploy the 2.5 seconds
Switch 4 - Lowers the monitor during the Deploy sequence for 3.75 seconds.
ON - Deploys for 3.75 seconds
OFF - Will not Deploy 3.75 seconds (factory set)
Note:
If Switch 3 and 4 are both ON the monitor will lower for 5 seconds during the Deploy
sequence.
Switch 5 - Allows the nozzle to return to straight stream during the Stow sequence.
ON - Returns the nozzle to straight stream during the Stow sequence
OFF - Leaves nozzle pattern set where last used (factory set)
Switch 6 - Reserved for Factory
Switch 7 - Allows the user to choose between the Learned positions or the Default positions.
ON - Stow at the Learned position (factory set)
OFF - Stow in the default position only
Switch 8 - Allows the user to turn the Learn mode ON or OFF
On - Enables Learn mode programming (factory set)
OFF - Disable the Learn mode, the user cannot reprogram a new setting
3
4
5
6
•
•
•
•
7
8
•
•