Anywire ASLINKAMP LA-A1AW Manual do produto - Página 8
Procurar online ou descarregar pdf Manual do produto para Terminais tácteis Anywire ASLINKAMP LA-A1AW. Anywire ASLINKAMP LA-A1AW 12 páginas. Anywireaslink system, analog input unit ch insulated type with 7-segment
■Reference point shift mode
This is a function to adjust an offset error between the connected analog
output device and this analog input unit.
Shift the reference point by a set reference point adjustment value.
- Address writer (ARW-04, ARW-03): Parameter 02
Variable
Reference point shift mode
0
Reference point shift mode OFF
Every time 0 is rewritten to 1, a reference point is adjusted to a
1
device being connected at the time and renewed to a new one.
Reference point shift mode ON
2
A reference point is xed to a point set with the variable 1 and
conversion operation starts.
When "address/parameter automatic setting" is used, the extension unit
follows only ON/OFF of the reference shift mode.
Renew the reference point for each unit.
When the value of the parameter 2 is rewritten from 0 to 1, the 7-segment
display in the reference point shift mode indicates input speci cations set at
the parameter 1.
Input
7-segment display
speci cations
0-10V
0-5V
1-5V
0-20mA
4-20mA
The average result of 32 times of voltage or current values input at this time
becomes the reference point adjustment value.
For AnyWireLink transmission, "measurement value - reference point
adjustment value" is stored as input data.
When the value of the parameter 2 is renewed to 1, the reference point shift
mode is turned ON.
While the value of the parameter 2 is 1, "CHG" and "Pr2" is alternately
displayed for 7-segment display.
Value of Parameter 2
Displaying the current input speci cations
(for about 1 second)
0→1
Value of Parameter 2
Changing to alternate display of "CHG" and "Pr2"
1 remains
Value of Parameter 2
Shifting to conversion operation by the reference point
1→2
shift and displaying an analog value to be input.
■Display example during operation
When receiving the transmission signal and starting, the unit displays set
input speci cations for about 3 seconds and then switches them to actual
input value display.
Ex.) When setting to 4-20 mA speci cation and operating
■When using as is
Displaying setting
speci cations
Displaying the input
measurement value
(Ex.) During 12 mA
conversion
Before shipment: 0
LED
Reference
indication
point
V ON
0V
LINK
V
mA
ALM
V ON
LINK
0V
V
mA
ALM
V ON
1V
LINK
V
mA
ALM
mA ON
0mA
LINK
V
mA
ALM
mA ON
4mA
LINK
V
mA
ALM
LINK
LINK
V
V
mA
mA
ALM
ALM
About 3 seconds
LINK
LINK
V
V
mA
mA
ALM
ALM
-L*A1AW 8/12-
■When using the reference point shift mode
Displaying the input
measurement value
Parameter 2
Changing 0 to 1
Renewing to the offset adjustment value
Parameter 2
Changing to 2
Displaying the input
measurement value
(Ex.) During 12 mA
conversion
Operating in the reference point shift mode
■When releasing the reference point shift mode
Displaying the input
measurement value
(Ex.) During 12 mA
conversion
Operating in the reference point shift mode
Parameter 2
Changing to 0
Releasing the reference point shift mode
isplaying the input
measurement value
(Ex.) During 12 mA
conversion
Parameter 2
When 1 continues
Alternately displaying
"CHG" and "Pr2"
[Data Structure]
Data (one word)
15
14
13
12
11
10
MSB
Conversion data (16bit binary data)
MAX output digital value: -200 to 16200 (FF38Hex* to 3F48Hex)
* The minus values are two's complement notation.
Effective output digital value: 0 to 16000 (0Hex to 3E80Hex)
LINK
LINK
V
V
mA
mA
ALM
ALM
LINK
LINK
V
V
mA
mA
ALM
ALM
LINK
LINK
V
V
mA
mA
ALM
ALM
About 3 seconds
LINK
LINK
V
V
mA
mA
ALM
ALM
LINK
LINK
V
V
mA
mA
ALM
ALM
LINK
LINK
V
V
mA
mA
ALM
ALM
About 3 seconds
LINK
LINK
V
V
mA
mA
ALM
ALM
LINK
LINK
V
V
mA
mA
ALM
ALM
About 3 seconds
LINK
LINK
V
V
mA
mA
ALM
ALM
0.6 second interval
9
8
7
6
5
4
3
2
1
0
LSB