IMPORTANT NOTICES
These call points carry the following approvals:
II 1 G Ex ia IIC T4 Ga -10°C to +55 °C
Ui=30 V, Ii=500 mA, Pi=1 W
Sira 04ATEX2350X
They are designed and manufactured to protect against other hazards as de ned in
paragraph 1.2.7 of Annex II of the ATEX Directive 2014/34/EU.
They are intended for indoor use within Intrinsically Safe (I.S.) Systems utilising suitable Safety
Barriers.
Special conditions for safe use (denoted by X after the certi cate number)
The enclosure is non-conducting and may generate an ignition-capable level of
electrostatic charges under certain extreme conditions. The user should ensure that the
equipment is not installed in a location where it may be subjected to external conditions
(such as high-pressure steam) which might cause a build-up of electrostatic charges on
non-conducting surfaces. Additionally, cleaning of the equipment should be done only
with a damp cloth.
The equipment may be used in an ambient temperature range of -10°C to +55°C.
These call points must not be modi ed in any way as doing so may invalidate the
Certi cation and may compromise the safety of the product.
© Apollo Fire Detectors Limited 2021
Apollo Fire Detectors Limited, 36 Brookside Road, Havant, Hants, PO9 1JR, UK
Tel +44 (0)23 9249 2412
Website: www.apollo- re.co.uk
39214-591/Issue 3
2813
2831
4
Conventional I.S. Indoor Manual Call Point
Installation Guide
General
Conventional I.S. Indoor Manual Call Point is available in two versions:
Part Number
Model Number
55100-031
MCP1A-R470SF-A071-01IS
Conventional Indoor Manual Call Point
The Conventional I.S. Indoor Manual Call Point is supplied with a backbox for surface
mounting. The call point is 'Type A' and is suitable for indoor use only. For ush mounting,
a standard electrical outlet box with a minimum depth of 25mm is required.
Installation – General
The installation must conform to BS5839: Part 1 (or applicable local codes).
Installation
1.
Fit the backbox (Fig 1) to the wall.
2.
Run the cables into the backbox and connect them to the terminal block as shown in
Fig 2. Ensure that functional earth/screen continuity is maintained.
3.
Unlock the small front cover by inserting the forked key and pushing it home. Remove
key, slide the cover down and remove the deformable element. Connect the terminal
block as shown in Fig. 2, secure the call point to the backbox and re t the deformable
element as required. Finally, replace the front cover in the reverse order in which it was
removed and push it up until it locks.
The call points should be installed in a position where they will not be subjected to
mechanical stresses and where the temperature is within operating temperature range.
Areas where there are, or are likely to be, aggressive substances should be avoided.
Product Name
Conventional I.S. Indoor Manual Call Point-Red
1