Apollo XPander XPA-CB-12034-APO Manual de colocação em funcionamento - Página 11
Procurar online ou descarregar pdf Manual de colocação em funcionamento para Alarme de fumo Apollo XPander XPA-CB-12034-APO. Apollo XPander XPA-CB-12034-APO 19 páginas. Diversity loop interface module
Também para Apollo XPander XPA-CB-12034-APO: Manual de instalação (2 páginas), Manual de instalação (2 páginas)
Menu Level: (1.4)
Fault Status
Alarm Status
Battery Level
Signal Level
Manual Update
Ident
Ch 1 LI
D = Device to Interface signal on channel 1
Ch 2 LI
D = Device to Interface signal on channel 2
Ch 1 LI
D = Interface to Device signal on channel 1
Ch 2 LI
D = Interface to Device signal on channel 2
Menu Level: (1.5)
Fault Status
Alarm Status
Battery Level
Signal Level
Manual Update
Ident
When selected, the signalling
Menu Level: (1.6)
Fault Status
Alarm Status
Battery Level
Signal Level
Manual Update
Ident
Menu Level: (1.7)
Fault Status
Alarm Status
Battery Level
Signal Level
Manual Update
Ident
Type
This menu shows the status of the two signalling channels used by the
loop interface and the communicating device. If more than one interface is
used, please refer to Appendix B on page 14.
The received signal strength at the loop interface from the device is shown
as LI D followed by a percentage indicating the signal strength. Similarly
the received signal at the device is shown as LI D followed by the signal
strength.
If you have moved or re-installed a device, complete a manual update
before checking the signal level.
The LI D level is updated every 300 seconds. The LI D level is updated
every 12 hours or when requested manually by selecting the "Manual
Update" option described below.
LI
D XXX
status of all devices is updated. The current status can then be viewed as
described in the "signal level" menu.
This menu shows the unique 5-digit identification number for the device.
This may be recorded on site drawings or the radio survey document for
maintenance purposes.
This menu indicates the detector type on a Combined Sounder Visual
Indicator Base.
© Apollo Fire Detectors Limited 2015
11
60 - 100 = Good signal level
50 - 59 = Medium Signal level*
40 - 49
= Low Signal level
30 - 39
= Caution Signal level
10 - 29
= Fault Signal Level
0
= No Signal level
*Minimum level recommended