MOUNTING INSTRUCTIONS

Wood Studded Wall
Once the location on the wall has been determined, inspect the wall
surface. The wall must be flat and square in the horizontal and vertical
plane to ensure the Great Lakes Wall Mounts closes correctly. If the
wall is not flat and square, the use of shims may be required.
Wood studded wall mounting instructions apply to a 2" x 4" wood stud
wall with 3/4" plywood.
Recommended Mounting Hardware for Wood Studded Wall
For WR2 and WR4:
Qty. (4) 1/4 x 2" long lag bolts and 1" O.D. flat washer
Masonry Wall Surface- For masonry wall surface, the installer must
provide all the appropriate hardware.
PROTECTIVE GROUNDING
Protective grounding studs are provided.
WARNING: To avoid injury to persons or loss of life, ground each
enclosure individually to the dedicated branch circuit ground.
Connecting Main Protective Grounding Stud to the Dedicated
Branch Circuit Ground- Connect the dedicated branch circuit ground
connector to the main protective grounding stud located inside on
the back of the rear section on the WR using a listed ring or
closed-loop terminal.
Parts Not Bonded to Protective Earthing Terminal- The following parts
are not effectively bonded to the protective earthing terminal: rails. If
these parts need to be bonded to the protective earthing terminal, do
so in accordance with Article 250 of the National Electrical Code.
M6 x 12mm
Ground stud