Adey Mini 230 Instalação e manutenção - Página 13
Procurar online ou descarregar pdf Instalação e manutenção para Bomba de água Adey Mini 230. Adey Mini 230 17 páginas. Digital pressurisation unit
10 TECHNICAL SPECIFICATION
General
Guarantee
Approvals
Features
System capacity
Mounting
Pump control system
Intelligent control interface
System fill mode
Dry run protection
Noise
Materials
Break tank
Front cover
Performance
Maximum Fill Pressure
Maximum flow
Maximum inlet pressure (tank fill valve)
Maximum working pressure
Ambient air temperature
Relative humidity
Min ./Max . water temperature
Water tank
Usable capacity
Inlet valve and fill rate
Fluid category
Cold water inlet (flexible hose)
Connections
Cold water outlet (flexible hose)
Overflow (compression fitting)
Pump
Number of pumps / pump mode
Pump type / motor type
Duty rating (unit)
Pump head and seal
Electrical
Power supply / phase / frequency
Power consumption
Current (full load)
Fuse rating
Power cable (pre-wired)
Alarm output
Physical
IP rating
Width
Depth
Height
Weight (including fittings)
Weight (filled)
ADEY reserve the right to amend the specification without notice .
Noise: The equivalent continuous A-weighted sound pressure level at a
10 .11
distance of 1 metre from the pump does not exceed 70 dB(A) .
Mini 130
Mini 230
CP1-03-04911
CP1-03-04912
2 year
CE
Up to 6,000 litres
Wall mount
✓
✓
✓
✓
-
-
✓
✓
60 dB(A)
60 dB(A)
Polyethylene
Acrylic capped ABS
3 . 0 bar (300 kPa)
1 l/min
7 bar (700 kPa)
6 bar
Min 4
o
C / Max 40
o
C
95 % non-condensing
Min 4
o
C / Max 23
o
C
2 litres
Torbeck (side entry) 12 l/min
CAT 5 (type AB air gap with weir)
G ½ male
15 mm compression x 600 flexible hose
G ¾ (19 - 23 mm diameter pipe)
1 / Duty
2 / Duty-standby
Solenoid / piston
Int 30 mins on/30 mins off (S3)
Continuous (S1)
PA66/POM NBR
230/1/50
100 Watts
0 .5 Amps
5 Amps
1 .5 metres
Single
IPX4
293 mm
145 mm
403 mm
3 . 6 Kg
4 .2 Kg
6 . 6 Kg
7 .2 Kg
- 24 -
11 TROUBLE SHOOTING GUIDE
Symptoms
Error Code
Probable Cause
No power to APU
Pump(s) not
starting
Low water
Low water in tank
System pressure =
set pressure
Sensor error
Pressure sensor fault
Pump(s) will not
System pressure set
stop
too high
Sensor error
Pressure sensor fault
Low pressure alarm
Leak in system .
triggered
Low pressure
Low pressure alarm
set too high .
Sensor error
Pressure sensor fault
High pressure
High pressure
System pressure
alarm triggered
too high
Sensor error
Pressure sensor fault
Sensor failure error
Sensor error
Pressure sensor
outside specifcation
Water overflowing
Water level too high
warning pipe or
Manifold NRV leaking
weir
Recommended Action
Ensure the green light is on the front of the APU, check fuse .
Depress float valve to varify water is filling tank, check water level and
supply .
APU functioning correctly . Check the set system pressure .
Remove pressure from the APU outlet and verify the displayed pressure
is 0 bar . Er will be displayed if the sensor signal is outside parameters .
(Replace sensor – call ADEY) .
System set pressure is set higher than the pump performance capability,
reduce set pressure . Ensure you have purchased the correct APU for the
system pressure required .
Remove pressure from the APU outlet and verify the displayed pressure
is 0 bar . Er will be displayed if the sensor signal is outside parameters .
(Replace sensor – call ADEY) .
Check system for leaks . Check for leaking pressure relief valve .
Reduce Low press alarm pressure . Check system pressure range during
normal operation .
Remove pressure from the APU outlet and verify the displayed pressure
is 0 bar . Er will be displayed if the sensor signal is outside parameters .
(Replace sensor – call ADEY) .
Check system operation . Increase High presure alarm set pressure .
Remove pressure from the APU outlet and verify the displayed pressure
is 0 bar . Error will be displayed if the sensor signal is outside parameters .
(Replace sensor – call ADEY) .
Remove pressure from the APU outlet and varify the displayed pressure
is 0 bar . Er will be displayed if the sensor signal is outside parameters .
(Replace sensor – call ADEY) .
Check function of the fill valve, replace or adjust if needed .
Isolate APU from system and mains water and replace non-return valve
and manifold .
- 25 -