ADF Web HD67506 Manual do utilizador - Página 12

Procurar online ou descarregar pdf Manual do utilizador para Equipamento industrial ADF Web HD67506. ADF Web HD67506 18 páginas.

ADF Web HD67506 Manual do utilizador
Industrial Electronic Devices

ETHERNET PROTOCOL:

This protocol is able to read and write frames in the ModBus net. This protocol is very simple; you must known only the "Type of Data", the
"Device Address" and the "Number of Point". When the device responds the answere is transferred into the Ethernet.
W
F
:
RITE
RAMES
The transmission has a fixed structure that consist of seven bytes plus the data.
n="Number of Point *2" if Type of Data is 0x10 or n="(Number of Point+7)/8" if Type of Data is 0x0F
The "Type of Data" (Byte Number 2) can have four values:
0x05: Write single Coil Status
0x06: Write single Holding Register
0x0F: Write multiple Coil Register
0x10: Write multiple Holding Register
ADFweb.com S.r.l.
Byte Number
Description
1
Write Identifier (Write=0x02)
2
Type of Data
3
Device Address
4
Start Address Hi
5
Start Address Lo
6
Number of Point Hi
7
Number of Point Lo
8÷n+1
Data
User Manual Modbus Master / Ethernet
Document code: MN67506_ENG
Revision 1.012
Page 12 of 18