Kohler 20RESD Manual de instruções de instalação e funcionamento - Página 12
Procurar online ou descarregar pdf Manual de instruções de instalação e funcionamento para Gerador portátil Kohler 20RESD. Kohler 20RESD 37 páginas.
1
APM PIB
2
Note:
See Figure 15 for maximum total cable length.
Note:
The APM, RXT, PIM, and/or load shed kit may be
equipped with an alternate single-row connector for
P10. See TP- 7239 for instructions to splice the PWR
and COM connections.
1. Factory connection, diode board to APM PIB.
2. Customer connections, generator 1 and generator 2 RDC2 controllers to APM diode board
3. Connect one end of each cable shield to GROUND.
4. Communication cable Belden #9402 or equivalent 20 AWG shielded, twisted-pair cable
5. Connect shields together.
6. Leave one end of each cable shield disconnected at the last device.
Figure 16 Communication (RBUS) Connection Details
12
3
DIODE BOARD
4
RXT
COM
PWR
B
A
GND
PIM
COM
PWR
B
A
6
COM
PWR
B
A
6
5
Load
shed kit
TT-1596
8/22