POWER REQUIREMENTS
TDC-100: 117VAC 10%, 50/60 Hz
TDC-100A: 234VAC 10%, 50/60 Hz
TDC-100B: 24VAC 10%, 50/60 Hz
12 VA typical (not including output load)
Fuse Type: 6.3A TR5 Time Delay (replaceable)
COMMAND SIGNAL INPUT
Input Impedance
Loss of Command threshold
Command Out of Range threshold
FEEDBACK SIGNAL INPUT
Input Voltage: 0 to 2.5 VDC
External Feedback Potentiometer: 1K ohm
POWER SUPPLY OUTPUTS
+15V OUT (J2-8): 100mA maximum (not including option module)
+5V OUT (J2-7): 20mA maximum
NOTE: Do not connect these outputs to other power supplies.
AC MOTOR OUTPUTS
Off-state Leakage Current: <15mA
Maximum Load Current @ 60C: 5A
ENVIRONMENTAL
Operating Temperature Range: 0 C to 60 C
Storage Temperature Range: -40 C to 85 C
Relative Humidity Range: 0 to 90 % (noncondensing)
www.atcontrols.com
SPECIFICATIONS
20K ohms (VOLTAGE CMD (+) Input)
251 ohms 1% (4-20 mA CMD (+) Input)
< 0.75V (1-5 VDC input)
< 1.5V (2-10 VDC input)
< 3mA (4-20mA input)
> 5.25V (0-5 VDC, 1-5 VDC input)
> 10.5V (0-10 VDC, 2-10 VDC input)
> 21mA (4-20mA input)