Aqua Mundus GreaseShield 1850 AST Manual de instalação

Procurar online ou descarregar pdf Manual de instalação para Sistemas de filtragem de água Aqua Mundus GreaseShield 1850 AST. Aqua Mundus GreaseShield 1850 AST 2 páginas.

Installation Guide - GreaseShield
"
0
Ensure that there is sufficient clearance above and to the right of the unit for servicing purposes
GS1850 AST Unit:
e
(5.9"/150mm minimum).
e
Inlet Pipe - 1½"/40mm:
Outlet Pipe - 2"/54mm:
0
Invert Inlet - 1¼"/32mm:
FlexiPlumb adaptor may be required. Should be capped off with a
0
Decant Outlet Hose - ¾"/18mm:
The Hose must be fixed in place using the drainage hose support provided.
Connected to the outlet of the unit; it is essential in the analysis of effluent leaving the unit.
Sampling Point:
The outlet of unit must be fitted with a running trap to reduce foul smells.
Running Trap:
Ensure that the container is not restricted or blocked for daily maintenance.
FOG Container:
Ensure that the container is not restricted or blocked for daily maintenance.
Solids Container:
Hot Water Solenoid Valve:
supply must not exceed
used. Mains water connections must be made via a WRAS approved isolation valve which follows a WRAS approved double
check valve.
The unit must be plugged into a
Power Lead:
Interconnecting Pipework:
Stainless Steel Hygiene Stand (Optional Extra):
stand. It can be adjusted up to
for cleaning.
Award Winning Technology
To be piped with a sufficient fall of no less than 1 in 40.
To be piped with a sufficient fall of no less than 1 in 40.
For gravity drained dishwashers use the invert inlet. A
To be piped directly into the main drainage pipe via a vented drainage stack as shown.
Hot water must be connected to the unit using the ¾"
pressure and
3 bar
60
C/140
°
13 amp
All pipework must be clipped and properly supported.
GS1850 AST unit should be installed on a Stainless Steel Hygiene
in height to allow the unit to be levelled on uneven surfaces and provide access
2"/50mm
1850 AST
®
FlexiPlumb Endcap when not in use.
1¼"/32mm
In the case of high pressure a pressure reducing valve must be
F.
°
rated
socket located below counter level.
IP56
0
1¼"/32mm to 1½"/40mm
Red PVC Hose provided, water
BSP {F/F)
Web: www.aquamundus.com Phone
number 01386832205 Email:
()
)
vs 04/02/2020