31.22
as defined by parameter
activation switch deactivates the STO. Any faults generated must be reset before restarting.
The STO function has a redundant architecture, that is, both channels must be used in the safety function implementation.
The safety data given is calculated for redundant use, and does not apply if both channels are not used.
WARNING! The STO function does not disconnect the voltage from the main and auxiliary circuits of the drive.
Notes:
If stopping by coasting is not acceptable, stop the drive and machinery using the appropriate stop mode before
activating the STO.
The STO function overrides all other functions of the drive.
Wiring
The safety contacts must open/close within 200 ms of each other.
Double-shielded twisted-pair cable is recommended for the connection. The maximum length of the cabling between the
switch and the drive control unit is 300 m (1000 ft). Ground the shield of the cable at the control unit only.
Validation
To ensure the safe operation of a safety function, a validation test is required. The test must be carried out by a competent
person with adequate expertise and knowledge of the safety function. The test procedures and report must be
documented and signed by this person. Validation instructions of the STO function can be found in the drive hardware
manual.

Technical data

Minimum voltage at IN1 and IN2 to be interpreted as "1": 13 V DC
STO reaction time (shortest detectable break): 1 ms
STO response time: 2 ms (typical), 5 ms (maximum)
Fault detection time: Channels in different states for longer than 200 ms
Fault reaction time: Fault detection time + 10 ms
STO fault indication (parameter
STO warning indication (parameter
Safety integrity level (EN 62061): SIL 3
Performance level (EN ISO 13849-1): PL e
The drive STO is a type A safety component as defined in IEC 61508-2.
For the full safety data, exact failure rates and failure modes of the STO function, refer to the drive hardware manual.
Markings
The applicable markings are shown on the type designation label of the drive.
CE
UL

Related documents

Document
ACS580-01 (0.75 to 250 kW, 1.0 to 350 hp) hardware manual
ACS580 standard control program firmware manual
ACx-AP-x assistant control panels user's manual
Drive composer PC tool user's manual
Converter module capacitor reforming instructions
. If the motor is running when Safe torque off is activated, it coasts to a stop. Closing the
31.22
) delay: < 500 ms
31.22
) delay: < 1000 ms
RCM
EAC
EIP green
WEEE
TÜV Nord
Code (English)
3AXD50000044794
3AXD50000016097
3AUA0000085685
3AUA0000094606
3BFE64059629
15
UKCA
CSA