a) Position the first section of spindle extension onto the operation point of the penstock
and align vertically in both planes.
b) Position the bracket at 150mm from the top of the extension.
c) Mark and drill the mounting holes for the brackets onto the wall, and fix using resin
anchors (follow resin manufacturer's instructions, delivered with the fixing kit).
d) Adjust the guide block on the bracket to ensure the extension remains vertical and
central to the penstock.
e) If multiple sections are used, join these together using the extension joint, using the
through bolt, and lock using the grub screw.
f) Repeat steps a-e as required.
g) Position and secure the locking ring 2mm below the top bracket- this stops the
extension stem from being removed.
h) At the top of the extension, fit a final extension joint to accept your operation selection.
Manual Key operation options
The T key and S Key options can be used either on the penstock itself or on a spindle extension. The
items are placed onto the operation point and turned manually as required. These are only suitable
up to a 600mm diameter due to water pressure and operation force required, but are ideal for
infrequent use or remote sites.
Pedestal options
Pedestals are used to position the operation point around waist height (900mm), to make it
comfortable and safe for operation at ground level.
All pedestal options are available for floor mounting or wall mounting, and on larger sizes, with a
Torque Booster, allowing wider use of handwheels and manual drives.
Operation & Maintenance Manual
APS-PE Penstock
Left: Floor mounted column, with Fascia Plate
Right: Floor mounted column, with Fascia plate removed, showing
Torque Booster option.
Below: Additional bracket to allow wall mounting