Installation
Optional
Current /
finishing
run power
device
Interface
1.5
Module
amps/85
watts
GBC
1.2
Advanced-
amps/340
Punch Pro
watts
High
0.8
Capacity
amps/70
Stacker (HCS)
watts
Standard
2 amps/70
Finisher
watts
Booklet
2 amps/70
Maker
watts
Finisher
SquareFold
0.4
Trimmer
amps/96
Module
watts
2-Knife
4 amps /
Trimmer
250 watts
Module
NOTE:
The Standard Finisher Plus requires two NEMA receptacles (NEMA 5-
15R or 5-20R).
Optional feeding /
Current
finishing device
(amps)
Standard
Finisher
1 amps
Finisher
Module
Plus
Finisher
5 amps
Transport
Electrical Requirements for the Print Servers
FreeFlow Print Server
Print Server
Current /
Item
run
power
Monitor
1.5 amp
25 watts
Controller
3.5
(hard drive)
amps
400
Watts
EX 2100 Print Server
Print Server
Current /
Voltage
Item
run
(VAC),
power
North
America
(NA)
Monitor
1.2 amp
100-240v
47-63 Hz
Controller
5 amps
100-240 V
(hard drive)
47/63 Hz
Customer Expectation and Installation Guide
Voltage
Power
Receptacle
(VAC)
cord
NEMA part
length
number
100-240
8.2
5-15R
feet/2.5
meters
100-240
8.2
5-15R
feet/2.5
meters
100-240
8.2
5-15R
feet/2.5
meters
100-240
8.2
5-15R
feet/2.5
meters
100-240
8.2
5-15R
feet/2.5
meters
100-240
8.2
5-15R
feet/2.5
meters
100-230
14.8
5-15R
feet/4.5
meters
Voltage
Power
(VAC)
cord
length
100-
8.2
240
feet/2.5
meters
100-
8.2
240
feet/2.5
meters
Voltage
Power
Receptacle
(VAC), North
cord
NEMA part
America
length
(NA)
100-240v
7.5
5-15R
feet/2.3
50/60 Hz
meters
+/-3Hz
100-240 V
7.5
5-15R
50/60 Hz
feet/2.3
meters
Power
Receptacle
cord
NEMA part
length
number
7.5
5-15R
feet/2.3
meters
7.5
5-15R
feet/2.3
meters
EX 2100 Print Server
Print Server
Item
Monitor
Controller
(hard
drive)
Determining the Amp/Circuit Requirements
Use the following formula to determine/calculate the amperage/circuit
requirements for all devices associated with the press (left and right
modules only); this includes the Print Server, Avanced HCF (single and
chanined), and optional finishing devices.
NOTE:
This formula does not calculate the press (left and right modules)
since it is on its own dedicated circuit.
1.
Determine the amps required for each device.
2.
Calculate the total amp sum of all the devices.
3.
The sum total is:
•
Receptacle
NEMA part
•
number
4.
Calculate the total number of devices associated with the press,
5-15R
including the Print Server, feeding, and all optional finishing devices.
This calculation is number of receptacles required. Refer to the
5-15R
following two examples.
Example 1
Device
FreeFlow Print Server Monitor: 1.5 amps
Controller (hard drive): 3.5 amps
OHCF
Interface Module
HCS
Total amount of
amps required
10.3 amps
Example 2
Device
FreeFlow Print Server Monitor: 1.5 amps
Controller (hard drive): 3.5 amps
OHCF
Interface Module
GBC AdvancedPunch Pro
HCS
nd
2
HCS
Booklet Maker Finisher
SquareFold Trimmer Module
Xerox Confidential
Current / run
Voltage
power
(VAC),
North
America
(NA)
1.2 amp
100-240v
47-63 Hz
0-8 amps
100-240 V
200 watts, 2
47/63 Hz
amps (typical)
400 watts, 3.5
amps (max)
12 or below; therefore, a 15 amp circuit may be used with NEMA 5-
15R. However, a 20 amp circuit is recommended using NEMA 5-
20R receptacles.
12.1 - 16; a 20 amp circuit is required (NEMA 5-20R receptacles).
Total number of required circuits
One 15 amp circuit with 5 receptacles (NEMA 5-
15R): 1 for each device.
You may consider using two 15 amp circuits: one
for the Print Server and the other for the
remaining devices; or one 20 amp circuit (NEMA
5-20R).
Xerox
Versant™ 2100 Press
®
Power
Receptacle
cord
NEMA part
length
number
7.5
5-15R
feet/2.3
meters
7.5
5-15R
feet/2.3
meters
Amps
5
3
1.5
0.8
Amps
5
3
1.5
1.2
0.8
0.8
2
0.4
36