ABB REF601 Manual do produto - Página 13

Procurar online ou descarregar pdf Manual do produto para Dispositivo de proteção ABB REF601. ABB REF601 20 páginas.

ABB REF601 Manual do produto
ABB
Feeder Protection
REF601 IEC
Product Version: 1.0
Conducted Immunity and Power unit tests
Slow High Energy Tran-
sient (Surge1.2/50us Volt-
age pulse)
Radio-Frequency distur-
bance (Including func-
tional earth port)
Voltage Dips.,Short Inter-
ruptions (ac)
Voltage Variation immu-
nity tests (ac)
Damped Oscillatory
Waves (HFD)
Ripple Voltage
Voltage Drop, Supply
Interruption and voltage
variations on d.c. input
power port (immunity
tests)
Power Frequency Immu-
nity Test
Radiated Immunity Tests
Radio-Frequency Electro-
magnetic Field (Ampli-
tude modulated)
Radio-Frequency Elec-
tromagnetic Field
from digital radio
telephones(Pulse Modul.)
IEC 61000-4-5
1.2/50μs pulse
IEC 60255-22-5
±4kVp (L-Gnd)
±2kVp (L-L)
IEC 60255-22-6
Level 3, 0.15...80MHz, step 1%, AM
80% @ 1kHz,.: 10Vrms/unmod (CM),
Spot freq 27MHz 68Mhz
IEC 61000-4-11
100% (10mS and 30mS),70% and 40%
IEC 61000-4-11
Voltage Test level 70%
IEC 61000-4-12
Level 3
1 MHz , 10 transients:± 2.5kVp (CM) ,
± 1kVp (DM)
IEC 60255-11
Level 3: 10% Un
IEC 61000-4-17
50, 300 Hz ripple freq.
IEC61000-4-29
100% @ 10ms and 100ms
IEC60255-22-7
Class A :
CM: 300Vrms
DM: 150Vrms
IEC 60255-22-3
80...1000MHz, AM 80% @ 1kHz, hori-
zontal and vertical polarization: - 10V/m
Spot freq: 80, 160, 450, 900MHz, AM 80%
@1kHz
IEC 60255-22-3
Level 4, 900 ± 5MHz, PWM 100% @ 200Hz,
50% D.C.: - 10V/m (10s Dwell time)
1MDB07207-YN C
13