10 SUMMARY MENU

The SUMMARY menu provides a simplified representation of the unit with a selec-
tion of the operating parameters (in real time), on the basis of the feedback from
the various probes installed.
NOTE: The top-left corner of each window shows which compressor is currently
providing the displayed data (U:1,2,3 o 4); to switch between compressors (only
possible from Master unit), refer to that explained in paragraph "3.3 Unit operating
status information (real time data) p. 7".

10.1 PAGE RELATING TO THE COOLING ONLY UNITS

— Indicates to which compressor the displayed data refers (U:1 = Master; U:2 =
Slave 1; U:3 = Slave 2; U:4 = Slave 3)
— Indicates the actual speed of the fans
— Indicates the current outside temperature
— Indicates the status of the pump (if it's active, the relative label is displayed) and
the temperature of the water entering the heat exchanger
— Indicates the current operating set-point for the unit
— Indicates the actual status of the compressors (those displayed are the currently
active compressors, if no compressor is "On" no label will be displayed)
— Indicates the actual high pressure value for the currently selected circuit
— Indicates the actual low pressure value for the currently selected circuit
— Indicates the temperature of the water leaving the heat exchanger
— Indicates the heat exchanger inlet water temperature

10.2 PAGE RELATING TO THE UNITS WITH FREECOOLING

— Indicates to which compressor the displayed data refers (U:1 = Master; U:2 =
Slave 1; U:3 = Slave 2; U:4 = Slave 3)
— Indicates the current outside temperature
— Indicates the temperature of the water leaving the heat exchanger
— Indicates the actual speed of the fans
— Indicates the actual status of the compressors (those displayed are the currently
active compressors, if no compressor is "On" no label will be displayed)
— Indicates the actual high pressure value for the currently selected circuit
— Indicates the actual low pressure value for the currently selected circuit
— Indicates the heat exchanger inlet water temperature
— Indicates the status of the pump (if it's active, the relative label is displayed)
18
10.3 PAGE RELATING TO THE UNITS WITH FREE GLYCOL
FREECOOLING
— Indicates to which compressor the displayed data refers (U:1 = Master; U:2 =
Slave 1; U:3 = Slave 2; U:4 = Slave 3)
— Indicates the current outside temperature
— Indicates the temperature of the water leaving the heat exchanger
— Indicates the actual speed of the fans
— Indicates the actual status of the compressors (those displayed are the currently
active compressors, if no compressor is "On" no label will be displayed)
— Indicates the actual high pressure value for the currently selected circuit
— Indicates the actual low pressure value for the currently selected circuit
— Indicates the heat exchanger inlet water temperature
— Indicates the status of the pump (if it's active, the relative label is displayed)

10.4 PAGE RELATING TO THE UNITS WITH RECOVERY

— Indicates to which compressor the displayed data refers (U:1 = Master; U:2 =
Slave 1; U:3 = Slave 2; U:4 = Slave 3)
— Indicates the current outside temperature
— Indicates the water temperature from the recovery outlet
— Indicates the temperature of the water leaving the heat exchanger
— Indicates the actual speed of the fans
— Indicates the actual status of the compressors (those displayed are the currently
active compressors, if no compressor is "On" no label will be displayed)
— Indicates the actual high pressure value for the currently selected circuit
— Indicates the actual low pressure value for the currently selected circuit
— Indicates the water temperature at the recovery inlet
— Indicates the heat exchanger inlet water temperature
— Indicates the status of the pump (if it's active, the relative label is displayed)