DIP-SWITCH CONFIGURATION
SETTINGS
To be done in the installation phase, only by expert personnel.
Some functions are not compatible with each other and, for
this reason, limits to Dip-Switch configurations have been set.
By turning on or off Dip-Switches inside the thermostat, we
get the following functions:
Sw1 Dip 1 (Default OFF )
Water valve fitted:
- Present, set (ON).
- Absent, set (OFF).
Sw1 Dip 2 (Default OFF )
Position of the water temperature probe:
- Water temperature probe positioned up line from the valve,
set (ON).
- Water temperature probe positioned down line from the
valve, set (OFF).
Sw1 Dip 3 (Default OFF )
Water valve management:
- Optimised, set (ON).
heating mode: valve closure delayed compared to the
turning off of the ventilation;
cooling: valve closure earlier than the turning off of the
ventilation.
- Normal, set (OFF).
Sw1 Dip 4 (Default OFF )
Probe adjustment:
- Fixed adjustment, set (ON).
- Dynamic correction, set (OFF),
calculated on the basis of the water temperature.
NOTES:>
* = In the fan coils with two valves installed in four-pipe systems the installation of a PLASMACLUSTER
-
For the proper functioning of the SA ambient probe make sure that Sw2 Dip3 is in the OFF position and the jumper JP1 at EXT Position.
Sw2
Sw1
JP1
ON
Sw1
OFF
8
Water valve present
Water temperature probe upline from the valve
Optimised water valve management:
Fixed probe correction
1 2 3 4
5
Dynamic Probe Correction
Normal water valve management:
Water probe downline from the valve
Water valve not fitted
Sw1 Dip 5 (Default OFF )
Heating mode enabling temperature:
- Reduced, set (ON).
Minimum water temperature 35 °C
- Normal, set (OFF).
Minimum water temperature 39 °C.
Sw1 Dip 6 (Default OFF )
Cooling mode enabling temperature:
- Reduced, set (ON).
Maximum water temperature 22°C
- Normal, set (OFF).
Maximum water temperature 17°C
Sw2 * Dip 1 (Default OFF)
Selection of the type of plant in which the fan coil is included:
- Four-pipe system, set (ON).
- Two-pipe system, set (OFF).
Sw2 * Dip 2 (Default OFF)
Presence of PLASMACLUSTER
- Present, set (ON).
- Absent, set (OFF).
Sw2 Dip 3 (Default OFF )
Air temperature probe enabling:
- Internal control panel probe,set (ON).
- Probe in fan coil, set (OFF).
Sw2 Dip 4 (Default OFF )
Option not available
®
Minimum water temperature 35°C in heating mode
Maximum water temperature 22°C in cooling mode
*
Four-pipe system
*
PLASMACLUSTER
Internal command panel probe
1 2
6
3 4
Probe in the fan coil
*
PLASMACLUSTER
*
Two-pipe system
Maximum water temperature 17 °C in cooling mode
Minimum water temperature 39 °C in heating mode
®
air purifier:
air purifier is not allowed.
®
present
Option not available
Sw2
Factory setting
®
not fitted