DSC PowerSeries PC1832 Руководство - Страница 6

Просмотреть онлайн или скачать pdf Руководство для Панель управления DSC PowerSeries PC1832. DSC PowerSeries PC1832 18 страниц. System enhancement module
Также для DSC PowerSeries PC1832: Руководство по установке (17 страниц), Руководство по установке (13 страниц), Руководство по установке (20 страниц)

DSC PowerSeries PC1832 Руководство
DSC Power Series PC1616 PC1832 PC1864 System Manual

Bypass Groups

A Bypass Group is a selection of zones programmed into the system. If you bypass a group of zones on a
regular basis, you can program them into the Bypass Group, so that you do not have to bypass each zone
individually every time. One Bypass Group can be programmed on each partition.
To program a Bypass Group:
1. Press [*][1], then your [access code] (if necessary).
2. Enter the two-digit numbers (01-64) of the zones to be included in the Bypass Group. On
PK5500/LCD5500 keypads, you can also use the [< >] keys to find the zone to be included in the
bypass group, and then press [*] to select the zone.
3. To save the selected zone into the group, press [9][5].
4. To exit bypassing mode and return to the Ready state, press [#].
To select a Bypass Group when arming the system:
1. Press [1][*], then your [access code] (if necessary).
2. Press [9][1]. The next time the system is armed, the zones in this group will be bypassed.
3. To exit bypassing mode and return to the Ready state, press [#].
Note: Bypass Groups are only recalled if the system is armed/disarmed after programming the bypass
group. This feature is not to be used in UL Listed installations.

Panic Alarms

Emergency Keys
Press the [F], [A] or [P] key for 2 seconds to generate a Fire, Auxiliary or Panic alarm. The keypad sounder
will beep indicating that the alarm input has been accepted and transmission to the central station is
underway. Ask your alarm company if the emergency keys are available on your system.
Note: The Fire keys can be disabled by the installer.
LED5511/LCD5511 Keypad
Press and hold both keys simultaneously for two seconds to send the following messages:
[1][3] Fire Message
[4][6] Auxiliary Message
[7][9] Panic Message

When Alarm Sounds

https://alpha.adt.com/help/61[11/12/2018 9:40:17 PM]